Panasonic CS-KE12NB41, CU-KE12NK1, CU-KE18NKU, CS-KE18NB4UW, CZ-18BT1U Checklist before Servicing

Page 63

11-2. Checklist before Servicing

Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of extrusion) by using the flare spacer.

Diameter of tube D

 

Specification A

Flare tool for R410A

 

Conventional flare tool (for R22)

 

 

 

 

 

 

Dia.1/4" (6.35 mm)

 

 

 

 

0 to 0.0196"

 

0.0472"

Dia.3/8" (9.52 mm)

 

 

(0 to 0.5 mm)

 

(1.2 mm)

Dia.1/2" (12.7 mm)

 

 

 

 

 

Dia.5/8" (15.88 mm)

 

 

 

 

 

 

 

Size of flare

D

A

Spacer

D

A

Flare tool for R410A

Conventional flare tool (R22)

Tubing precautions

Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation.

Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C.

No addition of compressor oil for R410A

No additional charge of compressor oil is permitted.

No use of refrigerant other than R410A

Never use a refrigerant other than R410A.

If refrigerant R410A is exposed to fire

Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure to provide ample ventilation during installation work.

Caution in case of R410A leak

Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room, immediately provide thorough ventilation.

63

Image 63
Contents 852 361 Outdoor Model No. Product Code NoSafety Precautions Prohibit Table of Contents CZ-RD515U CS-KE12NB41 & CZ-18BT1U + CU-KE12NK1Operating Range Temperature Indoor Air Intake Temp Outdoor Air Intake TempCS-KE12NB41 & CZ-18BT1U SpecificationsUnit Specifications Indoor UnitDimensions & Weight Outdoor Unit Dimensions & Weight Indoor Unit230V CU-KE18NKUCU-KE18NKU 208V CZ-KE18NB4UW & CZ-18BT1U Indoor Unit Panel CZ-18BT1U Major Component SpecificationsIndoor Unit Indoor Unit Body CS-KE12NB41CB-CS-KE18NB4U Indoor Unit Body CS-KE18NB4UWExternal Finish Outdoor UnitOutdoor Unit CU-KE12NK1 CompressorOutdoor Unit CU-KE18NKU Outdoor air temp sensor Other Component SpecificationsIndoor Unit CS-KE12NB41 & CZ-18BT1U Indoor air temp sensor ModelKTEC-35-S98Unit inch mm Dimensional DataUnit inch mm 852-0-0010-12700-0 Unit inch mm 852-0-0010-13200-0 Refrigerant Flow Diagram Refrigerant Flow DiagramOutdoor unit Outdoor unit Temperature Charts Performance DataIndoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1 High pressure performance chart Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU At wide Pressure Power Supply 115V Single Phase 60Hz Cooling Capacity Cooling CapacityCU-KE12NK1 CS-KE18NB4UW & CZ-18BT1U Power Supply 230V Single Phase 60Hz Cooling CapacityCooling Capacity Low Ambient 740 11,860 800 24.4 Power Supply 115V Single Phase 60Hz Heating Capacity Heating CapacityTH Total Heating Capacity BTU/h Power Supply 230V Single Phase 60Hz Heating Capacity Heating Electrical CharacteristicsElectrical Data CoolingVoltage208V Cooling Voltage230V CoolingCS-KE12NB41 18BT1U8FA2-5250-46900-2 Outdoor Unit CU-KE12NK1 8FA2-5251-12200-2 Controller Address Setting of the Remote Controller MaintenanceHow to Connect How to DisconnectDisassembly Procedure Disconnect the connectors in the control boxRemove the air intake grill Remove the ceiling panel Remove the power box and control box Remove the indoor air temperature sensorScrew Ground cable CN07 CN03 CN09 CN06 Remove the main body lower section Remove the heat exchanger sensor Remove the drain pump and float switchRemove the heat exchanger Remove the turbo fan and fan motorAuto cooling/heating operation FunctionsOperation Functions Emergency operationLamp colors Timer backupFreeze prevention Compressor discharge temperature controlProtective Functions Overload prevention during heatingDefrost detection and release CT Peak current cut-off controlReverse-Cycle Defrosting Troubleshooting Before Calling for Service Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Indoor Unit Self-diagnostics LampsReplace the circuit board or the fuse Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Replace the controllerCondition E01 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationFrom the previous page a Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Locations most susceptible to noise Trouble Correction Noise Malfunction and Electromagnetic InterferenceNoise malfunction Electromagnetic interferenceMeasurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorTo prevent the composition Configuration and characteristics of cylindersAmount in the charging cylinder is less than 20% ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing Systems
Related manuals
Manual 114 pages 38.6 Kb Manual 132 pages 33 Kb

CZ-18BT1U, CS-KE12NB41, CS-KE18NB4UW, CU-KE18NKU, CU-KE12NK1 specifications

The Panasonic CS-KE18NB4UW and CU-KE12NK1, along with the CS-KE12NB41, CZ-18BT1U, and CU-KE18NKU, represent a suite of advanced air conditioning solutions built with cutting-edge technologies designed to provide optimal comfort, energy efficiency, and air quality in various settings.

One of the standout features of this lineup is the inverter technology. Inverter air conditioners adjust the compressor speed to maintain the desired temperature efficiently. This leads to significant energy savings compared to traditional air conditioners, which tend to frequently cycle on and off, consuming more power. By continuously regulating the temperature, the Panasonic units not only save electricity but also prolong the lifespan of the compressor.

Another noteworthy characteristic is the nanoe™ technology integrated into some of these models. Nanoe™ technology uses hydroxyl radicals to purify the air, minimizing harmful bacteria and allergens. This makes the Panasonic units particularly suitable for users with allergies or respiratory issues, providing a cleaner and healthier indoor environment.

In terms of design, these models are sleek and compact, allowing them to fit seamlessly into any room decor, whether in a home, office, or commercial space. The quiet operation is another advantage, making them ideal for bedrooms and study areas where minimal noise is essential.

Furthermore, the CS-KE18NB4UW and CU-KE12NK1 offer a range of powerful cooling and heating capacities, making them versatile solutions for various climate conditions. The cold climate performance ensures consistent heating in colder regions, while the robust cooling capabilities make them perfect for hot summer months.

The user-friendly features include a smart remote control system, allowing users to adjust settings with ease from a distance. Some models are equipped with Wi-Fi capability, enabling integration with smart home systems for enhanced control and programmability.

In conclusion, the Panasonic CS-KE18NB4UW, CU-KE12NK1, CS-KE12NB41, CZ-18BT1U, and CU-KE18NKU air conditioning units exemplify innovation and efficiency. With their inverter technology, air purification features, compact designs, and smart functionalities, they stand out as ideal choices for maintaining comfortable and healthy indoor environments throughout the year.