hussman Q1-DC operation manual Plumbing, Refrigeration

Page 5

Rev. 0508

Plumbing

Waste Outlet and P-TRAP

The waste outlet is located off the center of the case on one side allowing drip piping to be run lengthwise under the fixture.

A 1-1/2” P-TRAP and threaded adapter are supplied with each fixture. The P-TRAP must be installed to prevent air leakage and insect entrance into the fixture.

NOTE: PVC-DWV solvent cement is recommended. Follow the Hussmann’s instructions.

Installing Condensate Drain

Poorly or improperly installed condensate drains can seriously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:

1.Never use pipe for condensate drains smaller than the nominal diameter of the pipe or P-TRAP supplied with the case.

2.When connecting condensate drains, the P-TRAP must be used as part of the condensate drain

to prevent air leakage or insect entrance. Store plumbing system floor drains should be at least 14” off the center of the case to allow use of the P-TRAP pipe section. Never use two water seals in series in any one line. Double P-TRAPS in series will cause a lock and prevent draining.

3.Always provide as much down hill slope (“fall”) as possible; 1/8” per foot is the preferred minimum. PVC pipe, when used, must be supported to maintain the 1/8” pitch and to prevent warping.

4.Avoid long runs of condensate drains. Long runs make it impossible to provide the “fall” necessary for good drainage.

5.Provide a suitable air break between the flood rim of the floor drain and outlet of condensate drain. 1” is ideal.

6.Prevent condensate drains from freezing:

a.Do not install condensate drains in contact with non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation material such as Armstrong’s Armaflex.

b.Where condensate drains are located in dead air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.

Refrigeration

Refrigerant Type

The standard refrigerant will be R-22 unless otherwise specified on the customer order. Check the serial plate on the case for information.

Piping

The refrigerant line outlets are located under the case. Locate first the electrical box, the outlets are then on the same side of the case, but at the opposite end. Insulate suction lines to prevent condensation drippage.

Refrigeration Lines

 

Liquid

Suction

3/8” O.D.

5/8” O.D.

NOTE: The standard coil is piped at 1/2” (suction); however, the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be 5/8”, 7/8”, or 11/8”. Refer to the particular case you are hooking up.

Refrigerant lines should be sized as shown on the refrigeration legend furnished by the store. Install P-TRAPS (oil traps) at the base of all suction line vertical risers.

Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.

Control Settings

See Q1-DC technical data sheet for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product temperatures. Product temperature should first be measured in the morning, after having been refrigerated overnight. For all multiplexing, defrost should be time terminated. Defrost length and frequency should be as directed in the Q1-DC technical data sheet. The number of defrosts per day should never change. The duration of the defrost cycle may be adjusted to meet conditions present at your location.

Access to TEV Valves and Drain Lines MECHANICAL - Remove product from case. Remove pans. TX valve (mechanical only) and drain are located under the pans within the case.

ELECTRONIC - The electronic expansion valve master and slave cylinder(s) are located within the electrical access panel(s) in the rear of case. Rear panels lift up and out.

NOTE: Duplex receptacles must be detached before removing rear panels.

Image 5
Contents Rev Deli Service CaseGeneral Instructions Table of ContentsCut and Plan Views InstallationDo not USE Permagum Installation ContdRefrigeration PlumbingElectrical Refrigeration ContdFinishing Touches Electrical ContdCase Cleaning When cleaningCleaning Glass and Mirrors User Information ContdNon-Glare Glass CleaningPlexiglass and Acrylic Care Antistatic CoatingsGlass Replacement and Adjustment Instructions MaintenanceEvaporator Fans CoilsQ1-DC Electrical Wiring DiagramsWiring DiagramsLoading Q1 DeliW1750002 Wiring Diagrams ContdDELIQ1 Q1DC-6RQ1DELI W1750003Loading 115 L1 4.9 #.# L2 #.# #.# L3 #.# #.#Loading W1750005L1 6.7 #.# L2 #.# #.# L3 #.# #.# W1750006 ContdBe Grounded W1750026Q1-DC-6R Diagrams ContdW1750007 Be Grounded Wiring Diagrams115 V L1 6.1 L2 L3 W1750009115 L2 L3 DWG # W1750010 Q1-DC-XS/Q1-DS-XS WiringQ1-DC-4S/Q1-DS-4S Q1-DC-5S/Q1-DS-5S Project Title Q1-DC-XS/Q1-DS-XSPRE-LIMINARY Subject to20392457 4W .29A Q1-DC-6S/Q1-DS-6SSubject to Change Q1-DC-7S/Q1-DS-7SQ1-DC-8S/Q1-DS-8S Q1-DC-9S/Q1-DS-9S M M Q1-DC-10S/Q1-DS-10STecumseh HGA9462ZXDXM 115VAC, 60HZ Q1-DC-11S/Q1-DS-11SW1750034-010 L2 L3 GfciAppendices Appendix A. Temperature Guidelines RefrigeratedAppendix B. Application Recommendations Refrigerated Open DisplayAppendix D. Recommendations to User Refrigerated Appendices ContdAppendices Contd Service Record