Panasonic CS-KS18NB4UW Troubleshooting Before Calling for Service, Method of Self-Diagnostics

Page 51

9. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE)

9-1. Precautions before Performing Inspection or Repair

After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.

High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF.

If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.

9-2. Method of Self-Diagnostics

Follow the procedure below to perform detailed trouble diagnostics.

NOTE

1:If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board, or a ROM socket insertion problem, or the ROM has not been installed.

2:The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics.

PROCEDURE

After turning on power to the air conditioner, use the remote controller and follow the steps below to execute self-diagnostics.

Step 1: Press and hold the remote controller HIGH POWER button and 1 HR TIMER button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release HIGH POWER and 1 HR TIMER buttons, "oP-1" (test run) appears, blinking in the remote controller clock display area.

Step 2: Next, press the 1 HR TIMER button once to change the display from "oP-1" to "oP-3" (self-diagnostics). (The display continues to blink.)

Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.

The self-diagnostics function utilizes the 3 indicator lamps on the main unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to report the existence of sensor trouble or a protective operation. (The lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.) Self-diagnostics is completed when the buzzer sounds 3 short beeps.

A maximum of 3 self-diagnostics reports are displayed, for 5 seconds each, beginning with the most recent report. Following this display the lamps turn OFF. In order to view the self-diagnostics results again, press the ON/OFF button again.

The 3 lamps remain OFF if no trouble has occurred.

<IMPORTANT> After self-diagnostics is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate if this is not done.

HIGH POWER button

<Clock display > Test run mode

Self-diagnostics mode

ON/OFF operation button

1HR.

TIMER button

ACL

(Reset) button

51

Image 51
Contents DC Inverter Split System AIR Conditioner Safety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Models CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKUModels CS-KS12NB41 & CZ-18BT1U + CU-KS12NK1A Outdoor Unit SpecificationsUnit Specifications Indoor UnitDimensions & Weight Indoor Unit 208V Unit Dimensions Height Inch mm 12-5/16 Outdoor Unit CU-KS12NK1A CS-KS12NB41 & CZ-18BT1UCU-KS12NK1A Outdoor Unit CU-KS18NKUA 230V CU-KS18NKUA Indoor Unit Outdoor Unit CU-KS18NKUA 208V Indoor Unit Panel CZ-18BT1U Major Component SpecificationsIndoor Unit Indoor Unit Body CS-KS12NB41CB-CS-KS18NB4U Indoor Unit Body CS-KS18NB4UWOutdoor Unit CU-KS18NKU Outdoor UnitControl Circuit Fuse 125V 25A Outdoor Unit CU-KS18NKUA Other Component Specifications Unit inch mm Dimensional DataUnit inch mm 852-0-0010-12600-0 CU-KS18NKUA Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor unit Outdoor unit Indoor Unit CS-KS18NB4UW & CZ-18BT1U Outdoor Unit CU-KS18NKUIndoor discharge air performance chart Temperature ChartsLow pressure performance chart Operating current performance chartTube Cooling Capacity Power Supply 115V Single Phase 60Hz Cooling CapacityPower Supply 230V Single Phase 60Hz Cooling Capacity CS-KS18NB4UW & CZ-18BT1UCU-KS18NKU or CU-KS18NKUA Cooling Capacity Low Ambient TC Total Cooling Capacity BTU/h Electrical Characteristics Electrical DataCooling Outdoor Unit Complete Unit Fan Motor CS-KS12NB41 18BT1U8FA2-5250-46900-2 Outdoor Unit CU-KS12NK1A 8FA2-5251-12300-2 BLK Outdoor Unit CU-KS18NKU CU-KS18NKUAAddress Setting of the Remote Controller MaintenanceHow to Connect How to DisconnectDisassembly Procedure Disconnect the connectors in the control boxRemove the air intake grill Remove the ceiling panel Remove the power box and control box Remove the indoor air temperature sensorScrew Ground cable CN07 CN03 CN09 CN06 Remove the main body lower section Remove the heat exchanger sensor Remove the drain pump and float switchRemove the heat exchanger Remove the turbo fan and fan motorPAM- control FunctionsOperation Functions Emergency operationLamp colors Timer backupCT Peak current cut-off control Compressor discharge temperature controlProtective Functions Freeze preventionTroubleshooting Before Calling for Service Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Indoor Unit Self-diagnostics LampsReplace the circuit board or the fuse Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Replace the controllerCondition E01 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationFrom the previous page a Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Noise Malfunction and Electromagnetic Interference Noise malfunctionElectromagnetic interference Measurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorAmount in the charging cylinder is less than 20% ExampleTo prevent the composition Case Refrigerant is Leaking Welding leaking pointsRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing Systems

CZ-18BT1U + CU-KS18NKU, CZ-18BT1U + CU-KS12NK1A, CZ-18BT1U + CU-KS18NKUA, CS-KS18NB4UW, CS-KS12NB41 specifications

The Panasonic CZ-18BT1U indoor unit, when paired with the appropriate outdoor units like CU-KS18NKU, CU-KS18NKUA, CU-KS12NK1A, CS-KS18NB4UW, and CS-KS12NB41, offers a robust solution for maintaining optimal indoor climates. These units are designed for residential and commercial applications, ensuring reliable heating and cooling performance.

One of the standout features of the Panasonic CZ-18BT1U is its energy efficiency. This model boasts a high Seasonal Energy Efficiency Ratio (SEER), enabling users to enjoy a comfortable environment without incurring excessive energy costs. This is further complemented by advanced inverter technology, which allows for variable speed operation, adjusting the compressor activity based on the cooling or heating needs of the space. This feature not only enhances comfort but also minimizes energy consumption.

The outdoor unit options, CU-KS18NKU, CU-KS18NKUA, and CU-KS12NK1A, support this efficiency with high-performance compressors designed for reduced noise levels. They are built to withstand varied weather conditions, ensuring durability and longevity. The outdoor units also feature high-efficiency heat exchangers that improve thermal performance, enhancing overall system efficiency.

Noise reduction is a critical consideration in HVAC systems, and the Panasonic CS-KS18NB4UW and CS-KS12NB41 outdoor units are engineered with this in mind. They operate at low decibel levels, making them ideal for residential areas where noise can be a concern. Additionally, these units come equipped with a wide range of operational modes, such as cooling, heating, and dehumidification, providing users with year-round comfort.

Flexibility and installation convenience are enhanced by the compact design of both the indoor and outdoor units. This versatility allows for various placement options, making them suitable for different room layouts.

Moreover, these systems incorporate air purification technologies, which help to improve indoor air quality by filtering out pollutants. This feature is especially beneficial for users with allergies or respiratory conditions, ensuring a healthier living environment.

In summary, the Panasonic CZ-18BT1U paired with CU-KS18NKU, CU-KS18NKUA, CU-KS12NK1A, CS-KS18NB4UW, and CS-KS12NB41 units offer an efficient and quiet HVAC solution. With advanced technologies, energy-saving features, and health-oriented design, they are a smart investment for maintaining comfort and improving air quality in any indoor space.