11-6. In Case Refrigerant is Leaking

CAUTION

(1) Detecting Leaks

Never attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant.

Use the detector for R410A to locate refrigerant leak points.

(2) Recovering refrigerant

Never release the gas to the atmosphere; recover residual refrigerant using the refrigerant recovery unit for R410A, instead.

(1) Detect leaks

OK

Do not reuse the recovered refrigerant because its composition will have been altered.

(3) Welding leaking points

Confirm again that no residual refrigerant exists in the unit before starting welding.

Weld securely using flux and wax for R410A.

Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen (N2) in the refrigerant circuit of the unit. Leave ends of tubes open during welding.

(2)Recover refrigerant

OK

(3)Weld leaking points

OK

(4) Checking for sealing

Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas.

(5) Evacuation

Use a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back.

The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly.

When using a vacuum pump with exhaust air volume more than 0.883 cu.ft./min. and ultimate vacuum pressure rate of 50 micron Hg.

(4)Check for sealing

OK

(5)Evacuation

OK

(6) Recharge

Standard time for evacuation

Length of tubing

Less than 33 ft. (10 m)

More than 33 ft. (10 m)

 

 

 

Evacuation time

More than 10 minutes

More than 15 minutes

(6) Recharging

Recharge unit in the same manner explained on the previous page "(5) Recharging."

67

Image 67
Contents DC Inverter Split System AIR Conditioner Safety Precautions Prohibit Table of Contents Checking Electrical Components Models CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKU Operating RangeModels CS-KS12NB41 & CZ-18BT1U + CU-KS12NK1A Outdoor Unit SpecificationsUnit Specifications Indoor UnitDimensions & Weight Indoor Unit 208V Unit Dimensions Height Inch mm 12-5/16 Outdoor Unit CU-KS12NK1A CS-KS12NB41 & CZ-18BT1UCU-KS12NK1A Outdoor Unit CU-KS18NKUA 230V CU-KS18NKUA Indoor Unit Outdoor Unit CU-KS18NKUA 208V Indoor Unit Panel CZ-18BT1U Major Component SpecificationsIndoor Unit Indoor Unit Body CS-KS12NB41CB-CS-KS18NB4U Indoor Unit Body CS-KS18NB4UWOutdoor Unit CU-KS18NKU Outdoor UnitControl Circuit Fuse 125V 25A Outdoor Unit CU-KS18NKUA Other Component Specifications Unit inch mm Dimensional DataUnit inch mm 852-0-0010-12600-0 CU-KS18NKUA Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor unit Outdoor unit Indoor Unit CS-KS18NB4UW & CZ-18BT1U Outdoor Unit CU-KS18NKUIndoor discharge air performance chart Temperature ChartsLow pressure performance chart Operating current performance chartTube Cooling Capacity Power Supply 115V Single Phase 60Hz Cooling CapacityCS-KS18NB4UW & CZ-18BT1U Power Supply 230V Single Phase 60Hz Cooling CapacityCU-KS18NKU or CU-KS18NKUA Cooling Capacity Low Ambient TC Total Cooling Capacity BTU/h Electrical Data Electrical CharacteristicsCooling Outdoor Unit Complete Unit Fan Motor 18BT1U CS-KS12NB418FA2-5250-46900-2 Outdoor Unit CU-KS12NK1A 8FA2-5251-12300-2 BLK Outdoor Unit CU-KS18NKU CU-KS18NKUAAddress Setting of the Remote Controller MaintenanceHow to Connect How to DisconnectDisconnect the connectors in the control box Disassembly ProcedureRemove the air intake grill Remove the ceiling panel Remove the power box and control box Remove the indoor air temperature sensorScrew Ground cable CN07 CN03 CN09 CN06 Remove the main body lower section Remove the heat exchanger sensor Remove the drain pump and float switchRemove the heat exchanger Remove the turbo fan and fan motorPAM- control FunctionsOperation Functions Emergency operationLamp colors Timer backupCT Peak current cut-off control Compressor discharge temperature controlProtective Functions Freeze preventionPrecautions before Performing Inspection or Repair Troubleshooting Before Calling for ServiceMethod of Self-Diagnostics Indoor Unit Self-diagnostics LampsReplace the circuit board or the fuse Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Replace the controllerCondition E01 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationFrom the previous page a Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Noise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Measurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorExample Amount in the charging cylinder is less than 20%To prevent the composition Welding leaking points Case Refrigerant is LeakingRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing Systems

CZ-18BT1U + CU-KS18NKU, CZ-18BT1U + CU-KS12NK1A, CZ-18BT1U + CU-KS18NKUA, CS-KS18NB4UW, CS-KS12NB41 specifications

The Panasonic CZ-18BT1U indoor unit, when paired with the appropriate outdoor units like CU-KS18NKU, CU-KS18NKUA, CU-KS12NK1A, CS-KS18NB4UW, and CS-KS12NB41, offers a robust solution for maintaining optimal indoor climates. These units are designed for residential and commercial applications, ensuring reliable heating and cooling performance.

One of the standout features of the Panasonic CZ-18BT1U is its energy efficiency. This model boasts a high Seasonal Energy Efficiency Ratio (SEER), enabling users to enjoy a comfortable environment without incurring excessive energy costs. This is further complemented by advanced inverter technology, which allows for variable speed operation, adjusting the compressor activity based on the cooling or heating needs of the space. This feature not only enhances comfort but also minimizes energy consumption.

The outdoor unit options, CU-KS18NKU, CU-KS18NKUA, and CU-KS12NK1A, support this efficiency with high-performance compressors designed for reduced noise levels. They are built to withstand varied weather conditions, ensuring durability and longevity. The outdoor units also feature high-efficiency heat exchangers that improve thermal performance, enhancing overall system efficiency.

Noise reduction is a critical consideration in HVAC systems, and the Panasonic CS-KS18NB4UW and CS-KS12NB41 outdoor units are engineered with this in mind. They operate at low decibel levels, making them ideal for residential areas where noise can be a concern. Additionally, these units come equipped with a wide range of operational modes, such as cooling, heating, and dehumidification, providing users with year-round comfort.

Flexibility and installation convenience are enhanced by the compact design of both the indoor and outdoor units. This versatility allows for various placement options, making them suitable for different room layouts.

Moreover, these systems incorporate air purification technologies, which help to improve indoor air quality by filtering out pollutants. This feature is especially beneficial for users with allergies or respiratory conditions, ensuring a healthier living environment.

In summary, the Panasonic CZ-18BT1U paired with CU-KS18NKU, CU-KS18NKUA, CU-KS12NK1A, CS-KS18NB4UW, and CS-KS12NB41 units offer an efficient and quiet HVAC solution. With advanced technologies, energy-saving features, and health-oriented design, they are a smart investment for maintaining comfort and improving air quality in any indoor space.