Fluke 561 Testing Radiant Heat Applications, Testing Water Heater Insulation, Testing Steam Traps

Page 18

561HVACPro

Users Manual

wall you should find parallel isothermal rows indicating the location of heat tubes below the surface. Perpendicular to the outside wall, you should find rising and falling temperatures at equal distances. High temperatures indicate you are scanning a heat tube beneath the floor surface, low falling temperatures indicate a space between the heat tubes.

1.Press Dand then press Ato select HI emissivity.

2.Press Cand then press Ato select MIN.

3.To locate radiant heat tubes in floor, temporarily elevate the loop temperature to create hotter spots for identifying tubing runs.

4.Before releasing trigger, press Ato toggle between MIN, MAX, DIF floor temperatures and record the temperatures for future comparison and trending under similar conditions.

Testing Radiant Heat Applications

1.Operate radiant heat loop until steady state conditions are achieved.

2.Attach the thermocouple to supply of radiant loop.

3.Record the supply temperature.

4.Attach thermocouple to return of radiant loop.

5.Record the return temperature.

6.Difference is Delta-T (temperature difference).

7.Repeat for each loop to zone and balance for equal Delta-T’s.

Testing Water Heater Insulation

1.Connect thermocouple probe to obtain ambient temperature near water heater.

2.Press Dand then press Ato select HI emissivity for vinyl jacketed insulation or painted metal jacketed water heaters.

3.Press Cand then press Ato select DIF.

4.Aim the Thermometer at the water heater.

5.Scan the water heater jacket.

6.Scan in horizontal rows from top to bottom

7.Press Cand then press Ato read MAX and DIF jacket temperatures. Record your readings.

The closer the jacket temperature is to ambient temperature, the less jacket losses there are.

Standby losses account for a majority of the water heater energy expenses. Increase water heater insulation to reduce standby losses.

Standby losses are losses when water is not being re-heated by the burners or the elements. When the water heater is idle (standing by) and no water is being drawn, heat loss through the jacket (and flue on oil/gas systems) are waste heat losses that can be reduced by increasing insulation and/or lowering the temperature setting.

Testing Steam Traps

Steam traps open on low temperature to allow steam flow to trap. Steam traps close at steam temperatures to stop steam flow. As steam temperature drops, traps open to allow more steam flow and to return (“drain”) condensate.

If temperature is low in steam pipe, low in trap and low in condensate return, trap may be stuck closed. If temperature is high in steam pipe, high in trap, and high in condensate return, trap may be stuck open.

If temperature is high in steam pipe, high in trap, and slightly lower in condensate return, trap is probably operating properly.

14

Image 18
Contents HVACPro Limited Warranty and Limitation of Liability Table of Contents HVACPro Introduction Contacting FlukeSafety Information WWarningFeatures FeaturesWhen the battery is low, B appears on the display DisplayButtons and Connector Buttons and ConnectorLocating a Hot or Cold Spot How the Thermometer WorksOperating the Thermometer Distance and Spot SizeOperating the Thermometer Field of ViewEmissivity Switching Between C and F Using the Contact Temperature Probe XWWarningMeasuring Dewpoint Temperature Typical MeasurementsTesting Insulated Return Ducts Typical MeasurementsScanning Walls for Air Leaks or Insulation Deficiencies Testing Fuses and Buss Connections Testing Contactors StartersTesting Enclosed Relays Testing Electrical ConnectionsTesting Bearings Testing Belts and SheavesChecking Hydronic Radiant Heat Applications Testing Radiant Heat Applications Testing Water Heater InsulationTesting Steam Traps Verifying Thermostat/Room Sensor Accuracy Superheat is a critical temperature Maintenance MaintenanceTroubleshooting CE CertificationSpecifications Infrared