Installation Procedure
6Installation of water drainage pipe
(1)Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm) Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening. If downward slope can't be made, take other measures to lift it up.
Keep a distance of
Slope over 1/100
Use the
Wind the drain hose to the clip using seal pad | 9 . |
Insulate drain hose in the room. | Large size seal pad 9 |
Clamp 1 | (accessory) |
|
| Clamp |
| (accessory) |
Tape (White) |
4mm below
<Cautions for the drain water lifting pipe>
Installation height shall be less than 280mm.
There should be a right angle with unit, 300mm from unit.
300mm below 1~1.5m Suspending bracket | |||
Drain hose |
| below280 | below |
(accessory) | drain water lifting pipe |
|
|
|
| 220 | 500 |
| Clamp |
|
|
(accessory)
75 below
500 below
Unit:mm
(Note)
(accessory)
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it. If several water hoses join together, do as per following proceedures.
100mmOver | Connect water hoses with a T joint. |
|
Specifieations of the water hoses shall meet the requirements for the unit running. Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200cc water to see water drainage.
20