Haier HBU-18CF03, HBU-18HF03 installation manual Wiring

Page 23

Installation Procedure

7Wiring

All supplied parts. materials and wiring operation must in appliance with local code and regulations.Use copper wire only.

When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians. A circuit breaker must be installed, which can cut power supply to all system.

Connecting of unit

Remove cover of control box , connect wires of correct pole to the terminal block inside,please connect the wires in right way.

Upon connecting, replace control box cover and inlet grill .

Note:remember to connect the blue terminal of indoor unit with the white terminal of outdoor unit properly using the connecting wire in the accesory bag(For heat pump model).Otherwise the "Run" light on indoor remote receiver will flash four times refer to Page.13.

Y/G

L N

POWER SUPPLY: 1PH,220-230V~,50Hz

INDOOR UNIT

TERMINAL BLOCK

1

2

3

4

Y/G

1(L)

2(N)

3

4

OUTDOOR UNIT

TERMINAL BLOCK

<<WARNING>>

Obscrve the following when connecting power supply terminal block:

Don't connect wires of different specifications to the same terminal block.

(Loose wire may cause overheating of circuit) Connect wires of same specifications as shown in right Fig.

Connect wires of the

Don't connect wires of

Don't connect wires

same specifications

the same specifications

of the different

at two sides.

at one side.

specifications.

8Wiring Example

As for outdoor unit circuit, please see Installation Manual of outdoor unit.

Note: All electric wires have their own poles, poles must match that on terminal block.

99. INSTALLATION OF ORNAMENT PANEL

Cautions for the installation

Be sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation. read also the Installation Manual of indoor unit. With this ornament , 2 or 3 air flow direction is not available.

Suitable height is 3 m.

Installation of ornament panel

Check if the indoor unit is horizontal with level apparatus,and also check if the size of ceiling opening is right. Remember to take off the level apparatus before installation.

Fix the ornament panel onto the indoor unit temporarily with two screws,make sure that the height difference of the indoor unit's two sides should be no more than 5mm.

Screw other two screws and tighten all of the four screws to fix up the ornamnet panel.

21

Image 23
Contents Cassette Type AIR Conditioner Contents Disposal of the old air conditioner Machine is adaptive in following situation Applicable ambient temperature rangeRefrigerating circuit is leak-proof Safety cautions Dont dismantle the outlet of the outdoor unit Operating noise WiringLocation Suction grill Introduction to Spare PartsSwing fender Outlet Air filterClean inlet grill MaintenanceClean air filter Dismantle and install swing plate Clean outlet and shellPre-season Care Seasonal ReservePost-season Care Followings are not malfunction Trouble ShootingIs the earth leakage breaker in action ? Power supply switch is not in on positionUnit fails to start Air filter too dirty ? When Trouble HappensInsufficient cooling or heating Insufficient coolingTrouble display Change-over switchCustomer Need-to-know Using DirectionsCustomer Need-to-know Installation tools Installation ProcedureMeanings of Warning and Cautions Preparation for the installation Selection of installation placeAfter installation on the ceiling Installation of indoor unitFix the paper pattern Insulate drain hose in the room Installation of water drainage pipeWiring Wires is right.Turn off the power for ten