Haier 0010557172, HFU-09H03/R2(DB), HFU-12HA03(B)/R1, HFU-18H03/R2(DB) Purging MethodFor R407C

Page 29

Installation Manual of Room Air Conditioner

3. Piping connection of the outdoor unit

Connecting the connecting pipe and inlet and

outlet liquid pipe according to the piping method

3-way valve

Gas Side

Purging Method:(For R407C)

Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.

12.7mm(1/2")

2-way valve

Liquid Side

 

 

6.35mm(1/4")

Gaugemanifold

Vacuum pump

Open the handle at low in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (low)

 

reach vacuum condition in a moment, check

again.

Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make

 

flaring work again, the return to the beginning of

.

Open

Close

Open the valve rod for the 2-way valve to an angle of anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make the inspection of gas leakage.

Service port

90ofor 6 sec.

3-way valve

2-way valve

Open

90o

No gas leakage?

In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed steps.

If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.

To prevent the gas leakage, turn the service port's cap, the valve rod's cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.

After attaching the each caps, check the gas leakage around the caps.

3-way valve

2-way valve

 

3-way valve

Service port cap

2-way valve

 

Valve rod cap

Valve rod cap

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to discharge all the refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

3-way valve

12.7mm(1/2")

2-way valve 6.35mm(1/4")

HFU-12HA03(B)/R1

2-way valve 6.35mm(1/4")

3-way valve 9.52mm(3/8")

HFU-09HA03(B)/R1

28

Image 29
Contents No.0010557172 Floor UnitDisposal of the packaging of your new air conditioner Applicable ambient temperature range SpecificationsMachine is adaptive in following situation Refrigerating circuit is leak-proofSafety Instruction OFF Strict Enforcement Indoor unit Parts and FunctionsOutdoor unit Filter insideAir flow selection When setting the air flow selection switch toWhen setting the air outlet selection switch to Remote Controller Parts and Functions Auto Operation Remote controllerOperation Then Select Cool operation Cool OperationThen Select DRY operation DRY OperationThen Select FAN operation FAN OperationAbout FAN operation Then Select Heat operation Heat OperationAdjusting the flap Adjusting the Air Flow DirectionSleep Operation Set clock correctly before starting Timer operation Timer On/Off OperationThen select your desired Timer mode Timer on OFF Timer On-Off OperationSoft Operation Power OperationNone 23 oC Unit startSetting method Power failure resumeplease set and apply as necessaryTo cancel Operation hintsCleaning of the unit MaintenanceMaintenance at the end of application season Before asking for service, check the following first Trouble shootingInstallation of outdoor unit Installation of indoor unitFloor fixing dimensions of the outdoor unitUnitmm Standard accessoriesTool necessary No. Shape and descriptionPiping connection of the indoor unit Piping connectionOpen Close Purging MethodFor R410APurging MethodFor R407C Wiring of indoor unit Electric wiringWiring of outdoor unit Outdoor unit PowerCut pipe Remove burs Insert the flare nut Flare pipe OthersFlare tooling die

HFU-12H03/R2(DB), HFU-12HA03(B)/R1, HFU-09H03/R2(DB), HFU-18H03/R2(DB), HFU-09HA03(B)/R1 specifications

Haier, a renowned global leader in home appliances, offers a variety of air conditioning units designed for optimal comfort and efficiency. Among its extensive range, the models 0010557172, HFU-09HA03(B)/R1, HFU-18H03/R2(DB), HFU-09H03/R2(DB), and HFU-12HA03(B)/R1 stand out due to their advanced features and technologies suitable for both residential and commercial applications.

The model 0010557172 serves as a prime example of Haier's commitment to energy efficiency. This unit boasts a high Energy Efficiency Ratio (EER), ensuring that it provides maximum cooling while minimizing electricity costs. The incorporation of intelligent inverter technology allows for seamless adjustments in cooling capacity, which not only enhances comfort but also reduces energy consumption.

The HFU-09HA03(B)/R1 is designed with user-friendly controls that allow for easy operation. Equipped with a remote control, this model provides convenience by allowing users to adjust settings from anywhere in the room. Its compact design makes it ideal for smaller spaces, promoting efficient use without compromising comfort. The inclusion of a sleep mode feature ensures quieter operation during the night, enhancing sleep quality.

In contrast, the HFU-18H03/R2(DB) is a powerful unit suitable for larger spaces. With its robust cooling capacity, it is perfect for environments where maintaining a constant temperature is crucial. This model features multi-functional modes, including cooling, heating, and dehumidification, offering year-round comfort regardless of external weather conditions. The unit also incorporates a smart filter system that effectively purifies the air, ensuring a healthier living environment.

The HFU-09H03/R2(DB) and HFU-12HA03(B)/R1 models emphasize durability and easy maintenance. Both models are equipped with self-cleaning technology, which automatically removes dust and impurities from the filter, prolonging the unit's lifespan. Additionally, these models are designed with an environmentally friendly refrigerant that complies with global regulations, minimizing their carbon footprint.

In summary, Haier's lineup of air conditioning units, including the 0010557172, HFU-09HA03(B)/R1, HFU-18H03/R2(DB), HFU-09H03/R2(DB), and HFU-12HA03(B)/R1, showcases a blend of innovative technologies and practical features. With a commitment to efficiency, comfort, and sustainability, Haier continues to meet the diverse needs of consumers in today's dynamic market, ensuring an optimal living and working environment.