Outdoor unit

5.Purging Method:To use vacuum pump

Liquid Side

Gas Side

6.35mm(1/4")

9.52mm(3/8")

 

12.7mm(1/2")

2-way valve

Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect

the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into

vacuum pump.

Tube(for R410A)

3-way valve

Gaugemanifold(for R410A)

Anti countercurrent joint

Vacuum pump(for R410A)

Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low)

reach vacuum condition in a moment, check again.

Open

Vacuumize for over 15min. And check the level gauge which should read -0.1 MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in gaugemanifold and stop the operation of the vacuum pump.

Close

Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of .

Open the valve rod for the 2-way valve to an angle of anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make the inspection of gas leakage.

In case of gas leakage, tighten

No gas leakage? parts of pipe connection. If leakage stops, then proceed

steps.

Detach the charge hose from the service port, open

2-way valve

3-way valve

Service port

Open

90

o

for 6 sec.

90o

 

If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder

Liquid Side

Gas Side

6.35mm(1/4")

9.52mm(3/8")

 

12.7mm(1/2")

2-way valve

3-way valve

 

HSU-07HEA03/R2

HSU-09HEA03/R2

HSU-09HEA103/R2

HSU-12HEA03/R2

HSU-18HEA03/R2

Liquid Side

Gas Side

6.35mm(1/4")

12.7mm(1/2")

2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.

 

3-way valve

90

2-way valve

3-way valve

2-way valve

To prevent the gas leakage, turn the service port's cap, the valve rod's cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.

After attaching the each caps, check the gas leakage around the caps.

HSU-22HEA03/R2

2-way valve 3-way valve

Valve rod cap

Service port cap Valve rod cap

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to discharge all the refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

2.Please do not let other cooling medium, except specified one (R410A), or air enter into the cooling circulation system. Otherwise, there will be abnormal high pressure in the system to make it crack and lead to personal injuries.

6

Image 7
Contents Installation Manual of Room Air Conditioner Selection of Installation Place Outdoor Unit Indoor unit Other direction piping Indoor unitConnecting the indoor/outdoor Electric Cable Connection of pipes Outdoor unitClose OpenInsert the flare nut Flare pipe Cut pipe Remove bursHerramientas necesarias para realizar la instalación Manual de instalación de aparato de aire acondicionadoFijación de la unidad exterior Selección de tuboSelección del lugar de instalación Fuente de alimentaciónUnidad interior Unidad interiorAl fijar por primera vez la placa de montaje Entubación en otra dirección Conexión de los cables eléctricos de interior/exterior Extraer la cubierta del cableadoConexión Unidad exteriorInstalación de la unidad exterior Conexión de los tubosAbrir Bomba de vacíoRebabas Puntos de pruebaTelecomando Batteria secca R-03 Attrezzi necessari per linstallazioneFissaggio dellelemento esterno Scelta del luogo di installazioneScelta del tuboe AlimentazioneComponente interno Componente internoDisegno del tubo Tubature con altre direzioni Collegamento del cavo elettrico per interni/esterni Asportazione della copertura dei fili elettriciConnessione Installazione del componente esternoComponente esterno Collegamento dei tubiChiude ApreTagliare il tubo Eliminare le Sbavature Controllo dellinstallazione e test di funzionamentoInserire il dado svasato Effettuare la svasatura del tubo Outils nécessaires à linstallation Manuel dinstallation du climatiseur de pièceFixation de lunité extérieure Dimensions de fixation au sol de lunité extérieure Unité mmChoix du tuyau Source dalimentationUnité intérieure Lors de la première installation de la plaque de fixationTuyauterie arrière Démontage facile pour nettoyage de lunité intérieure Unité intérieureFixer le corps de lunité intérieure Décharger le corps de lunité intérieurePuissance Branchement Installation de lunité extérieureUnité extérieure Branchement des tubesFermer Méthode de purge Pour utiliser unePompe à vide OuvrirInstallation de la source dalimentation IT Conformità Alle Direttive Europee PER I Modelli Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.ChinaES Conformidad Europea DE LAS Regulaciones Para LOS Modelos R410A GWP = Potencial de calentamiento global

HSU-07HEA03/R2, HSU-09HEA103/R2, 0010516146, HSU-22HEA03/R2 specifications

The Haier HSU series air conditioners, specifically the HSU-22HEA03/R2, HSU-09HEA103/R2, and HSU-07HEA03/R2 models, exemplify the brand's commitment to delivering efficient cooling solutions without compromising on comfort or energy consumption. These models incorporate a blend of advanced technologies and user-friendly features designed to cater to diverse climatic conditions and preferences.

One of the standout features of the HSU series is its energy-efficient design. The air conditioners boast high energy efficiency ratings, ensuring that users benefit from lower electricity bills while enjoying effective cooling. This efficiency is achieved through the implementation of inverter technology, which adjusts the compressor speed according to the cooling demand. This not only enhances performance but also significantly reduces noise levels, making for a more comfortable indoor environment.

Speaking of noise, Haier has prioritized quiet operation across the HSU series. The models are designed with sound-dampening technologies that keep operation to a minimum, allowing for a peaceful ambiance in homes and offices. This is particularly beneficial for bedrooms or shared spaces where noise can be a distraction.

The HSU series also incorporates a sophisticated air filtration system. The filters are designed to capture dust, pollen, and other airborne particles, improving indoor air quality. This feature is especially crucial for allergy sufferers and those looking to maintain a healthy living environment. Additionally, some models come equipped with a self-cleaning function, which helps to maintain the efficiency of the air conditioning unit and prolong its lifespan.

User convenience is another key characteristic of the HSU models. They come with intuitive remote controls that allow users to adjust settings such as temperature and fan speed from anywhere in the room. Furthermore, many models in the series feature programmable timers and sleep modes, ensuring optimal comfort without unnecessary energy consumption during the night.

The sleek and modern design of the HSU series units allows them to blend seamlessly into various room decors. They are compact and wall-mounted, making them suitable for both residential and commercial settings.

In summary, the Haier HSU-22HEA03/R2, HSU-09HEA103/R2, and HSU-07HEA03/R2 air conditioners are distinguished by their energy efficiency, quiet operation, advanced air filtration, and user-friendly features. With these models, Haier reinforces its reputation as a leading provider of innovative cooling solutions that prioritize comfort, efficiency, and indoor air quality.