Greenheck Fan ERH-90, ERH-55, ERH-45, ERH-20 manual Economizer APPLICATION/OPERATION

Page 10
Enthalpy Sensor
(Primary Sensor)
Timed Exhaust
Frost Control

ECONOMIZER APPLICATION/OPERATION

The energy recovery wheel may be de-energized for the purpose of providing economizer (free cooling) operation. This can be achieved with a signal from a Temperature or Enthalpy sensor mounted in the supply air inlet compartment (see FIGURE 13). This Primary sensor will de-energize the energy wheel when the outdoor air temperature (factory default is 65°F) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable set point. An additional Override temperature sensor is also furnished in the supply air inlet compartment to deactivate economizer mode (see FIGURE 13). The Override (with field adjustable set point) is set at some temperature lower than the Primary sensor (factory default is 50°F). Effectively, the two sensors create a deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into the building unconditioned.

Testing (terminals referenced below are in the unit control center — see FIGURE 5, Item #7)

 

Temperature sensor with Override

 

• Turn both Temperature and Override

 

thermostats down as low as they go.

FIGURE 13

The wheel should be rotating.

 

• Turn the Temperature sensor up as

 

high as it goes, and keep the Override

 

sensor as low as it will go. The wheel

 

should stop rotating.

• Turn both sensors as high as they will go. The wheel should start rotating.

• Set the Temperature sensor to the desired temperature for economizer operation to begin. Set the Override sensor to the desired temperature for economizer operation to end (factory default is 65°F and 50°F, respectively).

Override

Probes

Enthalpy sensor with Override

A factory-installed 620 ohm resistor is connected across terminals SR and +. The Override sensor should be turned

down below current temperature in unit. Turn the unit on; LED on the sensor should be off. Check continuity across terminals 2 and 3, there should not be continuity. There should be continuity between terminals 1 and 2.

Disconnect the 620 ohm resistor from terminals SR and +. LED should turn on. There should be continuity between terminals 2 and 3. There should not be continuity between terminals 1 and 2.

Turn the Override sensor above current temperature in unit. There should be continuity between terminals 3 and 6. Set the Override sensor to the desired temperature for economizer operation to end (factory default is 50°F).

Reconnect the factory-installed jumper.

10

Image 10
Contents Energy Recovery Wheel Heating Section Read and Save These InstructionsStorage Table of ContentsGeneral Lifting InstallationBasic Operation Recommended Roof OpeningRoof Curb Mounting Duct Work ConnectionsExhaust Dampers InstallationWeatherhoods Electrical ConnectionsService Clearances / Access Panel Locations for Model ERH TOP View Water Coil Location and Connection Water Coil Application RecommendationsElectric Heater APPLICATION/OPERATION Electric Post-HeaterFrost Control APPLICATION/OPERATION Dirty Filter Switch SetupTesting Timed exhaust frost control includes a thermostat withEconomizer APPLICATION/OPERATION General Start UP ChecksFAN Wheel Rotation FAN RPM Energy Recovery WheelCoils Motors Routine MaintenanceFAN Belts Wheel and FastenersInternal Filter Maintenance External Filter MaintenanceVibration Coil Maintenance Water Coil MaintenanceFilters Routine Energy Recovery Wheel Maintenance Maintenance of the Energy Recovery WheelRemoving the Energy Recovery Wheel Segments Parts List Model ERHTrouble Shooting Symptom Possible Cause Corrective ActionWarranty