Greenheck Fan ERH-20, ERH-55 Basic Operation, Installation, Lifting, Recommended Roof Opening

Page 3

BASIC OPERATION

The ERH brings in fresh, outdoor air and

Energy Recovery

removes stale, exhaust

Wheel

Exhaust Air

air. Prior to discharging the exhaust air, the energy recovery wheel transfers energy from the exhaust air to the outdoor air at an efficiency of 70-80%. Simply put, this unit preconditions the

Exhaust Air discharged outside

Outdoor Air

from building

outdoor air to save money on heating and cooling costs. This particular unit also has a heater option available after the recovery wheel to further increase the fresh air temperature if desired.

Optional

Heater

Preconditioned Air sent to conditioning system

INSTALLATION

The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook.

Adequate space should be left around the unit for piping coils and drains, filter replacement, and maintenance. Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary.

See page 6 for more detail on appropriate clearances.

LIFTING

Units must be lifted as it ships from the factory. All units are equipped with lifting lugs. THE USE OF ALL LIFTING LUGS IS MANDATORY WHEN LIFTING. Lifting should only be done with all access doors closed to avoid damaging the unit. To prevent damage to the unit cabinetry, use spreader bars. Spreader bars must be in position to stop cables from rubbing the frame or panels. Before hoisting into position, test lift to insure stability and balance. Avoid twisting or uneven lifting of the unit. Never lift units by weatherhoods.

Lift using lifting lugs and spreader bar

FIGURE 1

RECOMMENDED ROOF OPENING

UNIT WEIGHTS (dry weights)

TABLE 1

Model

U

V

ERH-20

46

37

ERH-45

54

39

ERH-55

65

47

ERH-90

85

49

Dimensions shown are in inches.

V

EXHAUST

INLET

SUPPLY

OUTLET

U

TABLE 2

Unit Size

Approx. Weight (lbs)

ERH-20

1000

ERH-45

1800

 

 

ERH-55

2500

 

 

ERH-90

4500

 

 

FIGURE 2

3

Image 3
Contents Read and Save These Instructions Energy Recovery Wheel Heating SectionTable of Contents StorageGeneral Recommended Roof Opening InstallationBasic Operation LiftingDuct Work Connections Roof Curb MountingElectrical Connections InstallationWeatherhoods Exhaust DampersTOP View Service Clearances / Access Panel Locations for Model ERHWater Coil Application Recommendations Water Coil Location and ConnectionElectric Post-Heater Electric Heater APPLICATION/OPERATIONTimed exhaust frost control includes a thermostat with Dirty Filter Switch SetupTesting Frost Control APPLICATION/OPERATIONEconomizer APPLICATION/OPERATION Start UP Checks GeneralFAN Wheel Rotation Energy Recovery Wheel FAN RPMCoils Wheel and Fasteners Routine MaintenanceFAN Belts MotorsExternal Filter Maintenance Internal Filter MaintenanceVibration Water Coil Maintenance Coil MaintenanceFilters Maintenance of the Energy Recovery Wheel Routine Energy Recovery Wheel MaintenanceRemoving the Energy Recovery Wheel Segments Model ERH Parts ListSymptom Possible Cause Corrective Action Trouble ShootingWarranty