ROOF CURB MOUNTING
1.Factory Supplied Roof Curbs
Roof curbs are Model GKD, which are shipped in a knockdown kit and require field assembly (by others). Assembly instructions are included with the curb.
2.Cut Roof Opening and Locate Curb
Layout the unit roof opening such that the supply discharge & exhaust inlet of the unit will line up with the corresponding ductwork (refer to Recommended Roof Openings on page 3). Be sure to allow for the recommended service clearances. Keep the supply inlet of the unit away from any other exhaust fans.
3.Install Curb
Locate curb over roof opening and fasten in place.
Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. Shim as required to level. Lower unit onto curb by following the LIFTING instructions on page 3 of this manual. Note,
roof curbs fit inside the unit base.
4. Install Duct Work | Model | L | W | |
|
|
| ||
Installation of all |
|
|
| |
73 | 51 | |||
ducts should be |
|
|
| |
80.75 | 60.63 | |||
done in accordance | ||||
|
|
| ||
94 | 71.5 | |||
with SMACNA and | ||||
106.25 | 90.75 | |||
AMCA guidelines. |
Dimensions shown are in inches.
L
W
FIGURE 3
Roof curb details, including duct location dimensions, are available on ERH roof curb submittals.
DUCT WORK CONNECTIONS
Examples of good and poor
R
|
| tio |
| a | |
t |
| |
o |
|
|
n
Length of Straight Duct |
|
|
| tion |
|
| a | ||
|
| t |
| |
| R | o |
|
|
|
|
|
|
GOOD
TABLE 4
|
|
| FIGURE 4 | ||
|
|
|
|
| |
| Recommended Discharge | ||||
|
| Duct Size and Length | |||
|
|
|
|
| |
ERH |
| ERH | Duct | Straight | |
| Blower | Duct | |||
Model | Size | ||||
Size | Length | ||||
|
|
| |||
|
|
|
|
| |
20 |
| 10 | 14 x 14 | 40 | |
45 |
| 12 | 20 x 20 | 48 | |
55 |
| 15 | 28 x 28 | 60 | |
90 |
| 18 | 32 x 32 | 72 |
Dimensions shown are in inches.
POOR
4