Trouble Shooting
Symptom | Possible Cause | Corrective Action | |
|
|
| |
| Blown fuse or open circuit | Replace fuse or reset circuit breaker and check amps. | |
| breaker. |
| |
Blower Fails to | Defective motor or capacitor. | Replace | |
|
| ||
Operate | Motor starter overloaded. | Reset starter and check amps. | |
| Electrical. | Check for On/Off switches. Check for correct supply voltage. | |
| Drive. | Check for broken or loose belts. Tighten loose pulleys. | |
|
|
| |
| Control power (24 Vac) wiring | Shorten wiring run to mechanical room or install a relay | |
| run is too long (resistance | which will turn unit on/off (C/F for relay information). | |
| should not exceed 0.75 ohms). |
| |
Motor Starters | Incoming supply power is | Need to increase supply power or use a special control | |
“Chatter” or Do | |||
less than anticipated. Voltage | transformer which is sized for the actual supply power. | ||
Not Pull In | |||
supplied to starter coil must |
| ||
|
| ||
| be within +10% / |
| |
| nominal voltage stated on |
| |
| the coil. |
| |
|
|
| |
| Cfm too high. | Check cfm and adjust drives if needed. | |
| Static pressures are higher or | If higher, ductwork should be improved. | |
| lower than design. | If lower, fan rpm should be lower. | |
Motor Over Amps | Blower rotation is incorrect. | Check rotation and reverse if necessary. | |
|
| ||
| Motor voltage incorrect. | Check motor nameplate versus supplied voltage. | |
| Motor horsepower too low. | See specifications and catalog for fan curves to determine if | |
|
| horsepower is sufficient. | |
| Shorted windings in motor. | Replace motor. | |
|
|
| |
| Unit damper not fully open. | Adjust damper linkage or replace damper motor. | |
| System static pressure too high | Improve ductwork to eliminate losses using good duct | |
|
| practices. | |
| Blower speed too low. | Check for correct drives and rpm with catalog data. | |
| Fan wheels are operating | For | |
Low Airflow (cfm) | backwards. |
| |
|
| ||
| Dirty filter or energy wheel. | Follow cleaning procedures on pages 14 and 17. | |
| Leaks in ductwork. | Repair. | |
| Elbows or other obstructions | Correct or improve ductwork. | |
| may be obstructing fan outlet. |
| |
| Belt slippage. | Adjust belt tension. | |
|
|
| |
| Blower fan speed too high. | Check for correct fan rpm. Decrease fan speed if necessary. | |
High Airflow (cfm) | Filter(s) not in place. | Install filters. | |
Insufficient static pressure (Ps) | Induce Ps into system ductwork. Make sure grilles and | ||
| |||
| (airflow resistance). | access doors are installed. Decrease fan speed if necessary. |
* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.
19