Remove these covers for horizontal duct applications
Return
Supply
Remove these panels for downflow duct applications
Duct Cover Installation
Down Discharge Applications
Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place.
NOTE: Single phase models require installation of horizontal duct kit #20464501PDGK (medium chassis) and #20464502PDGK (large chassis).
DUCT WORK
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Duct work should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit Dimension illustration in the appendix.
For
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
FILTERS
CAUTION
TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Filters are not provided with unit and must be supplied and exter- nally installed in the return duct system by the installer. An optional factory approved internal filter rack may also be used. A
Refer to the unit filter size chart below for filter size information.
MINIMUM FILTER SIZE
NOMINAL SIZE (INCHES) | NOMINAL AREA (SQ. FT.) |
10x20 | 1.4 |
14x20 | 1.9 |
14x25 | 2.4 |
15x20 | 2.1 |
16x20 | 2.2 |
16x25 | 2.8 |
20x20 | 2.8 |
20x25 | 3.5 |
25x25 | 4.3 |
NOTE: Filters must have adequate face area for the rated quantity of the unit. See the air delivery table below for recommended filter size. Size the filters in accordance with their manufacturer recom- mendations. Throwaway filters must be sized for a maximum face velocity of 300 feet per minute.
|
| 7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Area | Feet | 6 |
|
|
|
|
|
|
|
|
|
|
| R |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Filter |
|
|
|
|
|
|
|
|
|
|
| E |
|
|
|
|
|
| ||
5 |
|
|
|
|
|
|
|
|
| T |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| IL |
|
|
|
|
|
|
|
| ||||
Square |
|
|
|
|
|
|
|
| EF |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| L |
|
|
|
|
|
|
| R |
| |||
|
|
|
|
|
|
|
| B |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E |
| ||||
|
|
|
|
|
|
| A |
|
|
|
|
|
|
| T |
|
| |||
Nominal |
|
|
|
|
| S |
|
|
|
|
|
|
|
| IL |
|
|
| ||
4 |
|
|
| O |
|
|
|
|
|
|
|
| T |
|
|
|
| |||
|
| P |
|
|
|
|
|
|
|
| N |
|
|
|
| |||||
| IS |
|
|
|
|
|
|
|
| ANE |
|
|
|
|
| |||||
| D |
|
|
|
|
|
|
|
| M |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| R |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| E |
|
|
|
|
|
|
|
| ||
| 3 |
|
|
|
|
|
|
|
| P |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 2 | 1000 |
|
| 1500 | 2000 |
| 2500 |
| 3000 | 3500 | ||||||||
|
| 500 |
|
|
|
|
Airflow - SCFM
PIPING
CONDENSATE DRAIN
The condensate drain connection of the evaporator is a half cou- pling of ¾” N.P.T. A trap must be provided to have Proper conden- sate drainage.
Unit | 2" Minimum |
Drain |
|
Connection | 3" Minimum |
| |
Flexible |
|
A Positive Liquid Seal | |
Or Pipe | Is Required |
Install condensate drain trap as shown. Use ¾ “ drain connection size or larger. Do not operate without trap. Unit must be level or slightly inclined toward drain.