Goodman Mfg 3 Ton- 6 Ton CPC/CPH Series installation instructions CPC/H036 Direct Drive Down Shot

Page 17

APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

STANDARD DOWN SHOT AND HORIZONTAL

CPC/H036 DIRECT DRIVE DOWN SHOT

 

EXTERNAL STATIC

STANDARD

 

 

 

SPEED TAP

PRESSURE (ESP)

AMPS

WATTS

RPM

CFM

 

in w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

1287

1.66

350

770

 

0.20

1233

1.63

342

815

LOW

0.30

1176

1.59

332

858

0.40

1107

1.55

320

891

 

 

0.50

1044

1.51

312

924

 

0.60

965

1.45

296

957

 

0.10

1476

2.08

446

866

 

0.20

1421

2.03

432

885

 

0.30

1334

1.96

414

918

MED

0.40

1255

1.90

396

945

 

0.50

1180

1.84

386

971

 

0.60

1085

1.78

368

990

 

0.70

964

1.70

344

1023

 

0.30

1455

2.31

490

962

 

0.40

1367

2.25

476

984

HIGH

0.50

1277

2.16

454

1006

0.60

1180

2.09

438

1025

 

 

0.70

1080

2.02

418

1039

 

0.80

922

1.90

386

1067

CPC/H036 DIRECT DRIVE HORIZONTAL

 

EXTERNAL STATIC

STANDARD

 

 

 

SPEED TAP

PRESSURE (ESP)

AMPS

WATTS

RPM

CFM

 

in w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

1296

1.67

356

764

 

0.20

1245

1.60

334

830

LOW

0.30

1174

1.56

325

861

 

0.40

1103

1.52

316

891

 

0.50

1013

1.46

300

935

 

0.10

1502

2.10

456

836

 

0.20

1449

2.06

444

864

 

0.30

1396

2.02

432

891

MED

0.40

1335

1.97

418

916

 

0.50

1273

1.91

404

940

 

0.60

1153

1.83

380

973

 

0.70

996

1.71

346

1017

 

0.20

1516

2.36

506

940

 

0.30

1454

2.31

496

960

 

0.40

1392

2.26

486

979

HIGH

0.50

1273

2.17

458

1006

 

0.60

1183

2.09

441

1023

 

0.70

1092

2.02

424

1039

 

0.80

920

1.90

390

1067

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

3 Ton models are shipped from the factory with speed tap set on LOW.

17

Image 17
Contents TON 6 TON CPC/CPH Series Safety Instructions Replacement PartsHigh Voltage General InformationUnit Location Clearances Rigging Details Roof Curb POST-INSTALLATION ChecksRoof TOP Duct Connections Weights shown are belt drive with no accessories Rigging Removal Electrical WiringSupply Venting Condensate Drain Connection STARTUP, ADJUSTMENTS, and ChecksCirculating AIR and Filters Belt Drive Models only Drive Belt Tension Adjustment Heat Pump Operation Air Flow AdjustmentsMotor AIR Flow AdjustmentsPSC Motor Maintenance Drive Adjustments Motor Sheave AdjustmentsValve Body Damaged Replace valve ServiceCPC/H036 Direct Drive Horizontal CPC/H036 Direct Drive Down ShotCPC/H048 Direct Drive Horizontal CPC/H048 Direct Drive Down Shot790 CPC/H060 Direct Drive Down ShotCPC/H060 Direct Drive Horizontal CPC/H048 Standard Belt Drive Down Shot CPC/H036 Standard Belt Drive Down ShotCPC/H060 Standard Belt Drive Down Shot CPC/H072 Standard Belt Drive Down ShotCPC/H048 High Static Belt Drive Down Shot CPC/H036 High Static Belt Drive Down ShotCPC/H060 High Static Belt Drive Down Shot CPC/H072 High Static Belt Drive Down ShotCPC/H048 Standard Belt Drive Horizontal CPC/H036 Standard Belt Drive HorizontalCPC/H060 Standard Belt Drive Horizontal CPC/H072 Standard Belt Drive HorizontalCPC/H048 High Static Belt Drive Horizontal CPC/H036 High Static Belt Drive HorizontalCPC/H060 High Static Belt Drive Horizontal CPC/H072 High Static Belt Drive HorizontalAppendix B Electrical Data Unit Heater KIT Minimum CFM Model Number Minimum AIR Flow for Electric HeatAppendix C Unit Dimensions 2010,2012 Goodman Manufacturing Company, L.P