Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit

Page 20

APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

STANDARD CPC/H060 HORIZONTAL

CPC/H060 DIRECT DRIVE HORIZONTAL

SPEED

EXTERNAL STATIC

STANDARD

 

 

 

PRESSURE (ESP)

AMPS

WATTS

RPM

TAP

CFM

in w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

1355

1.57

174

599

 

0.20

1281

1.66

182

651

 

0.30

1235

1.76

196

693

 

0.40

1168

1.81

202

726

T1

0.50

1118

1.94

218

775

 

0.60

1049

2.03

232

819

 

0.70

982

2.10

240

858

 

0.80

922

2.14

246

885

 

0.90

871

2.25

260

927

 

0.10

1544

2.04

234

660

 

0.20

1490

2.17

250

704

 

0.30

1427

2.25

260

742

 

0.40

1370

2.35

276

781

T2

0.50

1319

2.42

282

809

 

0.60

1274

2.52

296

849

 

0.70

1210

2.62

316

891

 

0.80

1137

2.73

326

935

 

0.90

1106

2.77

336

957

 

0.10

2099

4.13

516

825

 

0.20

2068

4.25

536

852

 

0.30

2029

4.37

552

885

T3

0.40

1971

4.48

568

913

0.50

1911

4.61

586

950

 

0.60

1876

4.73

604

973

 

0.70

1821

4.86

622

1012

 

0.80

1792

4.91

630

1028

 

0.90

1740

5.03

648

1067

 

0.10

2233

4.76

608

863

 

0.20

2168

4.91

628

896

 

0.30

2125

5.02

640

924

 

0.40

2070

5.14

660

951

T4

0.50

2050

5.27

678

979

 

0.60

1980

5.41

696

1012

 

0.70

1954

5.47

704

1034

 

0.80

1893

5.60

724

1067

 

0.90

1852

5.70

736

1089

 

0.10

2322

5.44

710

904

 

0.20

2294

5.55

726

934

 

0.30

2254

5.68

742

958

 

0.40

2201

5.80

766

990

T5

0.50

2147

5.93

782

1017

 

0.60

2117

6.01

788

1039

 

0.70

2081

6.12

808

1060

 

0.80

2017

6.22

822

1094

 

0.90

1932

6.10

804

1111

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

20

Image 20
Contents TON 6 TON CPC/CPH Series Replacement Parts Safety InstructionsGeneral Information High VoltageUnit Location Clearances Rigging Details Roof Curb POST-INSTALLATION ChecksRoof TOP Duct Connections Weights shown are belt drive with no accessories Electrical Wiring Rigging RemovalSupply Venting Condensate Drain Connection STARTUP, ADJUSTMENTS, and ChecksCirculating AIR and Filters Belt Drive Models only Drive Belt Tension Adjustment Air Flow Adjustments Heat Pump OperationMotor AIR Flow AdjustmentsPSC Motor Drive Adjustments Motor Sheave Adjustments MaintenanceService Valve Body Damaged Replace valveCPC/H036 Direct Drive Down Shot CPC/H036 Direct Drive HorizontalCPC/H048 Direct Drive Down Shot CPC/H048 Direct Drive HorizontalCPC/H060 Direct Drive Down Shot 790CPC/H060 Direct Drive Horizontal CPC/H036 Standard Belt Drive Down Shot CPC/H048 Standard Belt Drive Down ShotCPC/H060 Standard Belt Drive Down Shot CPC/H072 Standard Belt Drive Down ShotCPC/H036 High Static Belt Drive Down Shot CPC/H048 High Static Belt Drive Down ShotCPC/H060 High Static Belt Drive Down Shot CPC/H072 High Static Belt Drive Down ShotCPC/H036 Standard Belt Drive Horizontal CPC/H048 Standard Belt Drive HorizontalCPC/H060 Standard Belt Drive Horizontal CPC/H072 Standard Belt Drive HorizontalCPC/H036 High Static Belt Drive Horizontal CPC/H048 High Static Belt Drive HorizontalCPC/H060 High Static Belt Drive Horizontal CPC/H072 High Static Belt Drive HorizontalAppendix B Electrical Data Minimum AIR Flow for Electric Heat Unit Heater KIT Minimum CFM Model NumberAppendix C Unit Dimensions 2010,2012 Goodman Manufacturing Company, L.P