Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit

Page 18

APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

STANDARD DOWN SHOT AND HORIZONTAL

CPC/H048 DIRECT DRIVE DOWN SHOT

 

EXTERNAL STATIC

STANDARD

 

 

 

SPEED TAP

PRESSURE (ESP)

AMPS

WATTS

RPM

CFM

 

in w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

1602

2.48

528

835

 

0.20

1538

2.37

506

878

LOW

0.30

1474

2.26

484

921

 

0.40

1390

2.15

460

950

 

0.50

1306

2.04

436

979

 

0.10

1805

2.84

620

935

 

0.20

1704

2.71

590

967

 

0.30

1625

2.59

558

990

MED

0.40

1549

2.47

540

1012

 

0.50

1437

2.38

516

1030

 

0.60

1301

2.23

480

1050

 

0.70

1158

2.09

444

1072

 

0.10

1971

3.22

706

968

 

0.20

1828

3.03

664

998

HIGH

0.30

1744

2.94

632

1017

0.40

1628

2.80

606

1034

 

 

0.50

1510

2.69

582

1050

 

0.60

1402

2.57

552

1067

CPC/H048 DIRECT DRIVE HORIZONTAL

 

EXTERNAL STATIC

STANDARD

 

 

 

SPEED TAP

PRESSURE (ESP)

AMPS

WATTS

RPM

CFM

 

in w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

1622

2.54

539

809

 

0.20

1558

2.43

517

852

LOW

0.30

1494

2.32

495

895

 

0.40

1410

2.21

471

924

 

0.50

1326

2.10

447

953

 

0.10

1861

3.11

670

886

 

0.20

1733

2.78

606

918

 

0.30

1639

2.64

568

960

MED

0.40

1564

2.51

542

984

 

0.50

1434

2.35

508

1017

 

0.60

1320

2.25

482

1039

 

0.70

1156

2.08

446

1067

 

0.10

1984

3.34

734

949

 

0.20

1883

3.18

694

977

HIGH

0.30

1770

3.03

654

1001

0.40

1656

2.87

620

1027

 

 

0.50

1540

2.76

590

1044

 

0.60

1415

2.62

558

1061

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

4 Ton models are shipped from the factory with speed tap set on MED.

18

Image 18
Contents TON 6 TON CPC/CPH Series Replacement Parts Safety InstructionsGeneral Information High VoltageUnit Location Clearances Roof Curb POST-INSTALLATION Checks Roof TOP Duct ConnectionsRigging Details Weights shown are belt drive with no accessories Electrical Wiring Rigging RemovalSupply STARTUP, ADJUSTMENTS, and Checks Circulating AIR and FiltersVenting Condensate Drain Connection Belt Drive Models only Drive Belt Tension Adjustment Air Flow Adjustments Heat Pump OperationAIR Flow Adjustments PSC MotorMotor Drive Adjustments Motor Sheave Adjustments MaintenanceService Valve Body Damaged Replace valveCPC/H036 Direct Drive Down Shot CPC/H036 Direct Drive HorizontalCPC/H048 Direct Drive Down Shot CPC/H048 Direct Drive HorizontalCPC/H060 Direct Drive Down Shot 790CPC/H060 Direct Drive Horizontal CPC/H060 Standard Belt Drive Down Shot CPC/H036 Standard Belt Drive Down ShotCPC/H048 Standard Belt Drive Down Shot CPC/H072 Standard Belt Drive Down ShotCPC/H060 High Static Belt Drive Down Shot CPC/H036 High Static Belt Drive Down ShotCPC/H048 High Static Belt Drive Down Shot CPC/H072 High Static Belt Drive Down ShotCPC/H060 Standard Belt Drive Horizontal CPC/H036 Standard Belt Drive HorizontalCPC/H048 Standard Belt Drive Horizontal CPC/H072 Standard Belt Drive HorizontalCPC/H060 High Static Belt Drive Horizontal CPC/H036 High Static Belt Drive HorizontalCPC/H048 High Static Belt Drive Horizontal CPC/H072 High Static Belt Drive HorizontalAppendix B Electrical Data Minimum AIR Flow for Electric Heat Unit Heater KIT Minimum CFM Model NumberAppendix C Unit Dimensions 2010,2012 Goodman Manufacturing Company, L.P