Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit

Page 24

APPENDIX A BLOWER PERFORMANCE TABLES

BELT DRIVE

HIGH STATIC HORIZONTAL

CPC/H036 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

1742

 

0.50

1431

 

0.36

0.8

 

 

 

 

 

 

 

 

 

 

1626

 

0.52

1357

 

0.39

1078

 

0.27

1

 

 

 

 

 

 

 

1611

 

0.56

1315

 

0.42

1011

 

0.28

 

 

 

1.2

 

 

 

 

1605

 

0.62

1299

 

0.46

976

 

0.31

 

 

 

 

 

 

1.4

 

1605

 

0.68

1281

 

0.51

959

 

0.35

 

 

 

 

 

 

 

 

 

1.6

 

1281

 

0.57

981

 

0.41

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

981

 

0.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H048 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

2056

 

0.72

1721

 

0.54

0.8

 

 

 

 

 

 

 

 

 

 

1996

 

0.77

1662

 

0.57

1328

 

0.40

1

 

 

 

 

 

 

 

1924

 

0.79

1603

 

0.61

1270

 

0.43

 

 

 

1.2

 

 

 

 

1952

 

0.88

1559

 

0.64

1210

 

0.44

 

 

 

 

 

 

1.4

 

1888

 

0.92

1543

 

0.70

1195

 

0.49

 

 

 

 

 

 

 

 

 

1.6

 

1557

 

0.77

1180

 

0.54

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

1192

 

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H060 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

 

0

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2323

 

0.92

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

2315

 

1.00

2009

 

0.77

1

 

 

 

 

 

 

 

 

 

 

2308

 

1.09

1992

 

0.84

1666

 

0.60

1.2

 

 

 

 

 

 

 

2338

 

1.21

1992

 

0.92

1646

 

0.66

 

 

 

1.4

 

 

 

 

2359

 

1.32

2025

 

1.02

1648

 

0.72

 

 

 

 

 

 

1.6

 

2404

 

1.45

2056

 

1.13

1684

 

0.82

 

 

 

 

 

 

 

 

 

1.8

 

2088

 

1.24

1722

 

0.92

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H072 HIGH STATIC BELT DRIVE HORIZONTAL

ESP, In

 

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

 

2

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

2746

 

1.38

2515

 

1.12

0.8

 

 

 

 

 

 

 

 

 

 

2721

 

1.47

2494

 

1.21

2261

 

0.97

1

 

 

 

 

 

 

 

2689

 

1.56

2500

 

1.32

2255

 

1.06

1994

 

0.83

1.2

 

 

 

 

2752

 

1.74

2473

 

1.40

2252

 

1.15

1996

 

0.91

 

 

 

1.4

 

2802

 

1.88

2487

 

1.53

2286

 

1.27

2037

 

1.02

 

 

 

 

 

 

1.6

 

2553

 

1.67

2308

 

1.40

1997

 

1.08

 

 

 

 

 

 

 

 

 

1.8

 

2355

 

1.51

2014

 

1.19

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

2055

 

1.29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

24

Image 24
Contents TON 6 TON CPC/CPH Series Replacement Parts Safety InstructionsGeneral Information High VoltageUnit Location Clearances Roof Curb POST-INSTALLATION Checks Roof TOP Duct ConnectionsRigging Details Weights shown are belt drive with no accessories Electrical Wiring Rigging RemovalSupply STARTUP, ADJUSTMENTS, and Checks Circulating AIR and FiltersVenting Condensate Drain Connection Belt Drive Models only Drive Belt Tension Adjustment Air Flow Adjustments Heat Pump OperationAIR Flow Adjustments PSC MotorMotor Drive Adjustments Motor Sheave Adjustments MaintenanceService Valve Body Damaged Replace valveCPC/H036 Direct Drive Down Shot CPC/H036 Direct Drive HorizontalCPC/H048 Direct Drive Down Shot CPC/H048 Direct Drive HorizontalCPC/H060 Direct Drive Down Shot 790CPC/H060 Direct Drive Horizontal CPC/H036 Standard Belt Drive Down Shot CPC/H048 Standard Belt Drive Down ShotCPC/H060 Standard Belt Drive Down Shot CPC/H072 Standard Belt Drive Down ShotCPC/H036 High Static Belt Drive Down Shot CPC/H048 High Static Belt Drive Down ShotCPC/H060 High Static Belt Drive Down Shot CPC/H072 High Static Belt Drive Down ShotCPC/H036 Standard Belt Drive Horizontal CPC/H048 Standard Belt Drive HorizontalCPC/H060 Standard Belt Drive Horizontal CPC/H072 Standard Belt Drive HorizontalCPC/H036 High Static Belt Drive Horizontal CPC/H048 High Static Belt Drive HorizontalCPC/H060 High Static Belt Drive Horizontal CPC/H072 High Static Belt Drive HorizontalAppendix B Electrical Data Minimum AIR Flow for Electric Heat Unit Heater KIT Minimum CFM Model NumberAppendix C Unit Dimensions 2010,2012 Goodman Manufacturing Company, L.P