Goodman Mfg SSZ140181A service manual 51.54

Page 24

HEATING SPECIFICATIONS

Model: SSZ140421A* / CA*F4860*6A*+TXV / MBR2000**-1

Conditions: 1400 CFM Indoor Air @ 70°F DB

Outdoor

Basic Unit without

 

Capacity of Unit*

 

Auxiliary Heat

 

With KW of Auxiliary heat

 

Ambient

 

 

 

 

 

 

 

°F.

capacity

 

 

 

 

 

 

 

btuh

c.o.p.

4.8

9.6

14.4

 

19.2

65

51.54

4.44

67.92

84.30

100.68

 

117.07

60

48.79

4.28

65.17

81.55

97.94

 

114.32

55

45.92

4.11

62.30

78.68

95.07

 

111.45

50

42.93

3.92

59.31

75.69

92.07

 

108.46

45

39.73

3.70

56.11

72.49

88.88

 

105.26

40

36.90

3.50

53.28

69.66

86.05

 

102.43

35

34.03

3.30

50.41

66.79

83.18

 

99.56

30

34.27

3.26

50.65

67.03

83.41

 

99.79

25

31.63

3.08

48.01

64.39

80.77

 

97.15

20

29.12

2.90

45.50

61.89

78.27

 

94.65

15

26.48

2.70

42.86

59.25

75.63

 

92.01

10

23.76

2.48

40.14

56.52

72.91

 

89.29

5

21.07

2.25

37.45

53.83

70.21

 

86.59

0

18.37

2.01

34.75

51.13

67.52

 

83.90

-5

15.68

1.76

32.06

48.44

64.82

 

81.20

-10

12.84

1.48

29.22

45.61

61.99

 

78.37

Model: SSZ140481A* / CA*F4860*6A*+TXV / MBR2000**-1

Conditions: 1550 CFM Indoor Air @ 70°F DB

Outdoor

Basic Unit without

 

Capacity of Unit*

 

Auxiliary Heat

 

With KW of Auxiliary heat

 

Ambient

 

 

 

 

 

 

 

°F.

capacity

 

 

 

 

 

 

 

btuh

c.o.p.

4.8

9.6

14.4

 

19.2

65

57.82

4.25

74.20

90.59

106.97

 

123.35

60

54.74

4.10

71.12

87.50

103.89

 

120.27

55

51.52

3.94

67.90

84.28

100.67

 

117.05

50

48.16

3.76

64.54

80.93

97.31

 

113.69

45

44.57

3.55

60.96

77.34

93.72

 

110.10

40

41.40

3.36

57.78

74.16

90.55

 

106.93

35

38.18

3.17

54.56

70.94

87.33

 

103.71

30

36.62

2.94

53.00

69.38

85.76

 

102.15

25

33.80

2.77

50.18

66.56

82.94

 

99.32

20

31.12

2.61

47.50

63.89

80.27

 

96.65

15

28.30

2.43

44.68

61.06

77.45

 

93.83

10

25.39

2.24

41.77

58.16

74.54

 

90.92

5

22.51

2.03

38.89

55.28

71.66

 

88.04

0

19.63

1.82

36.01

52.40

68.78

 

85.16

-5

16.75

1.59

33.13

49.52

65.90

 

82.28

-10

13.72

1.34

30.11

46.49

62.87

 

79.25

Model: SSZ140601A* / CA*F4860*6A*+TXV / MBE2000**-1

Conditions: 1850 CFM Indoor Air @ 70°F DB

Outdoor

Basic Unit without

 

Capacity of Unit*

 

Auxiliary Heat

 

With KW of Auxiliary heat

 

Ambient

 

 

 

 

 

 

 

°F.

capacity

 

 

 

 

 

 

 

btuh

c.o.p.

4.8

9.6

14.4

 

19.2

65

71.65

4.34

88.03

104.41

120.80

 

137.18

60

67.83

4.19

84.21

100.59

116.98

 

133.36

55

63.84

4.03

80.22

96.60

112.99

 

129.37

50

59.68

3.85

76.06

92.44

108.83

 

125.21

45

55.23

3.64

71.62

88.00

104.38

 

120.76

40

51.30

3.45

67.68

84.06

100.45

 

116.83

35

47.31

3.26

63.69

80.07

96.46

 

112.84

30

47.86

3.17

64.24

80.63

97.01

 

113.39

25

44.17

2.99

60.56

76.94

93.32

 

109.70

20

40.68

2.83

57.06

73.44

89.83

 

106.21

15

36.99

2.63

53.37

69.76

86.14

 

102.52

10

33.19

2.43

49.57

65.95

82.34

 

98.72

5

29.42

2.21

45.81

62.19

78.57

 

94.95

0

25.66

1.98

42.04

58.42

74.81

 

91.19

-5

21.90

1.74

38.28

54.66

71.04

 

87.43

-10

17.94

1.46

34.32

50.70

67.09

 

83.47

*To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU)

24

Image 24
Contents Technical Information Manual 036 Product IdentificationProduct Identification Product Design AA AALight Commercial Heat Pump Specifications SSZ140181A* SSZ140601ACooling Performance Data SSZ140181ASSZ140181A Cooling OperationSSZ140241A SSZ140241A IDBSSZ140301A SSZ140301A 28.8368 151SSZ140361A SSZ140361A 34.28SSZ140421A 13.4 13.8 14.3 SSZ140481A SSZ140481A SSZ140601A SSZ140601A 56.0Performance Data 18,000 13,203 797 483Split System Heating Performance Expanded Performance DataOutdoor Ambient Temperature 41.0Heating Specifications Capacity Btuh19.2 51.54 Performance Test Wiring Wiring is subject to change