PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the Heat Pump Specifications.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

NOTE: Pressures are measured at the liquid and suction service valve ports.

25

Image 25
Contents Technical Information Manual Product Identification 036Product Identification AA AA Product DesignLight Commercial SSZ140181A* SSZ140601A Heat Pump SpecificationsSSZ140181A Cooling Performance DataCooling Operation SSZ140181ASSZ140241A IDB SSZ140241ASSZ140301A 28.8 SSZ140301A368 151SSZ140361A 34.28 SSZ140361ASSZ140421A 13.4 13.8 14.3 SSZ140481A SSZ140481A SSZ140601A 56.0 SSZ140601A18,000 13,203 797 483 Performance DataExpanded Performance Data Split System Heating Performance41.0 Outdoor Ambient TemperatureCapacity Btuh Heating Specifications19.2 51.54 Performance Test Wiring is subject to change Wiring