Amana 10730418 Normalsequenceofoperation, Startup and Adjustment, Condensate Drain

Page 7

Figure 12 - Horizontal Duct Cover Installation

DUCTWORK

Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.

A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Con- ditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.

The warm air supply duct from the unit through a wall fabricated of combustible material may be installed without clearance. However, minimum clearances for the unit must be observed as shown in Prod- uct Data Book applicable to your model*.

The outlet duct should be provided with an access panel.

For vertical airflow, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the PRC roof curb installation manual.

If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.

FILTERS

CAUTION

TO AVOID PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT A FILTER INSTALLED.

be filled either before a cooling startup or during a unit “cycle-off” after 20 minutes of running on first cycle. This drain can be ex- tended using 3/4” PVC piping.

1-1/2" Minimum drop at outlet

90° ELL

Condensate

Drain Trap 2-1/2" of

3/4" PVC

Figure 13 - Condensate Drain Connection

NORMALSEQUENCEOFOPERATION

NOTE: There is a fan delay on initial power to unit before the low voltage board resets and is operational.

1.Thermostat calls for heating or cooling. The compressor and outdoor fan are energized.

2.Approximately 10 seconds later, the indoor fan starts.

3.The unit will deliver heating or cooling to the conditioned space until the thermostat is satisfied.

NOTE: PHD60 Two-Stage Cooling

If the room temperatures is 4°F higher than thermostat setpoint, the indoor fan will run at high speed, and the compressor at full load. If the room temperature is within 2°F of thermostat setpoint; the indoor fan will shift to low speed and the compressor will unload to a lower capacity.

4.The compressor and outdoor fan will be de-energized when the thermostat opens.

5.The indoor fan continues to run for approximately 30 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor fan stops.

STARTUP AND ADJUSTMENT

Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air.

Refer to Product Data Book applicable to your model* for filter size information.

If using the Over/Under Transition Kit, the filter(s) may be located in the return air duct(s) or return air filter grille(s). Filters installed exter- nal to the unit should be sized in accordance with their manufacturer recommendations. A throwaway filter must be sized for a maximum face velocity of 300 feet per minute.

FILTER INSTALLATION

Important: When installing a filter, the air flow arrows on the filter must point toward the circulating air blower.

CONDENSATE DRAIN

WARNING

TO PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT THE ELECTRICAL POWER BEFORE INSPECTING OR SERVICING THE UNIT. SINCE ALL OF THE COMPRESSOR PROTECTION DEVICES RESET AUTOMATICALLY, THE CONTACTOR AND OUTDOOR FAN MAY BE ENERGIZED WHEN RESET.

CAUTION

THIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER" DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURES AND EXPOSURE TO VERY DIRTY ATMOSPHERES.

CONDENSATE DRAIN CONNECTION

An external condensate drain trap is required with this unit. See your distributor for details. For proper unit operation, the trap must

COMPRESSOR PROTECTION DEVICES

The PHB**C and PHD**C compressor includes components which are designed to protect the compressor against abnormal operating conditions.

7

Image 7
Contents Package Heat Pump Installation Instructions Recognize Safety SYMBOLS, WORDS, and Labels Safety InstructionsRigging and Handling General InformationDuct Connections Horizontal Airflow InstallationsThermostat Placement Thermostat WiringDownshot Airflow Conversion Flexible Wiring SetupCirculating AIR and Filters Unit VoltagePHD48/60 and PHB60 Models Horizontal Duct Cover InstallationNormalsequenceofoperation Startup and AdjustmentCondensate Drain Accessories Maintenance

10730418 specifications

The Amana 10730418 is a prominent appliance within the realm of home cooling solutions, specifically designed to enhance indoor air quality and comfort. This model exemplifies the blend of modern technology and practical functionality. One of its primary features is the inclusion of a robust cooling system, which effectively regulates temperature, ensuring a consistent and comfortable environment.

A standout aspect of the Amana 10730418 is its advanced energy efficiency. Equipped with a high Seasonal Energy Efficiency Ratio (SEER) rating, this model promises lower energy consumption without compromising cooling performance. This not only translates to reduced utility bills but also reinforces a commitment to environmental sustainability. The incorporation of energy-efficient technologies makes it a wise choice for discerning homeowners focused on minimizing their ecological footprint.

The cooling unit is integrated with a multi-speed fan that provides customizable airflow options, allowing users to select the perfect setting to suit their immediate needs. Whether one desires a gentle breeze or a powerful blast of cool air, the Amana 10730418 can easily adapt, ensuring comfort during any season. Additionally, the unit features a quiet operation mode designed to minimize noise, thereby enhancing the overall living experience.

In terms of control, the Amana 10730418 includes a user-friendly interface that simplifies operation. Many models come with programmable thermostats, allowing users to schedule cooling cycles in advance, ultimately saving energy during those times when cooling is not needed. This feature is particularly handy for busy households, enabling automated adjustments that align with daily routines.

The durability of the Amana 10730418 should also be noted. Constructed with high-quality materials and designed for long-term reliability, this appliance is built to withstand the rigors of daily use. Maintenance is made easier through features like removable filters that can be cleaned or replaced as needed, ensuring optimal performance over an extended lifespan.

Overall, the Amana 10730418 stands out as a comprehensive solution for anyone seeking to enhance their home's climate control systems. Its combination of energy efficiency, customizable performance, and user-friendly features make it an ideal choice for modern living. With this appliance, homeowners can confidently achieve a comfortable, efficient, and enjoyable indoor environment.