Bard T**H*D, W**H*D, S**H*D installation instructions Thermostat Wire Size

Page 4

 

 

TABLE 4

 

HUMIDITY CONTROLS

 

 

 

Part Number

 

Predominate Features

8403-038

 

SPDT switching, pilot duty 50VA @ 24V

(H600A1014)

 

Humidity range 20-80% RH

8403-047

 

Electronic dehumidistat SPST closes-on-rise

(H200-10-21-10)

 

Humidity range 10-90% with adjustable stops

 

TABLE 5

 

CO2 CONTROLLER

 

 

Part Number

Predominate Features

 

Normally Open SPST relay closes-on-rise

 

24V dual wave length sensor. Default setting

8403-067

950ppm, adjustable to 0-2000ppm

 

Default off setting 1000ppm, adjustable to

 

0-200 ppm can be calibrated

TABLE 6

THERMOSTAT WIRE SIZE

Transformer

 

Wire

Maximum

FLA

Distance

VA

Gauge

 

In Feet

 

 

 

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 gauge

160

 

 

12 gauge

250

Manual

2100-516H

Page

4 of 19

Image 4
Contents Single Stage Heat Pumps LOW Voltage Control Circuit Wiring Contents Wiring LOW Voltage Wiring Thermostat Wire Size Low Voltage Wiring Diagram Low Voltage Wiring Diagram Stage Cool Only if optional CO2 controller is used Low Voltage Wiring Diagram Electronic Programmable Stage Cool Stage Heat Cool CRV Stage Cool 2 Stage Heat WH/SH Heat Pump Connection Diagram WH Unit Low Voltage Term. Strip Thermostat 24V Low Voltage Terminal Block Yellow Black Red Stage Cool Stage Heat Unit