EMI WLHA, S1C manual Units with Condensation Pumps

Page 32

Troubleshooting procedure Continued

Optional Heat pump

with Electric Heat

Continued

EMI heat pump systems utilize a reversing valve is that is energized in the cooling mode. The reversing-valve signal is provided through the orange (O) low volt wire of the air handler or thermostat. It should remain energized constantly as long as the indoor unit or thermostat remains in cooling mode. To check for 24v reversing valve voltage, at the outdoor unit, place a voltmeter across the brown (C) and orange (O) wires while in the cooling mode.

heating: Heat pump units can accommodate two-stage heating when an optional electric strip heater is present along with a heat pump condenser. The first stage being the compressor and the second is electric heat. The air handler or wall thermostat will cycle the condenser through the yellow (Y) wire as it does in cooling however the reversing valve will not be energized. To check for a condenser signal, place the indoor unit or wall thermostat in heating. Next place the set-point temperature one degree above room temperature to call the first stage of heating. Then, with a voltmeter check for 24 volts across the yellow (Y) and brown

(C)wires at the condenser. The electric heat should be off at this point. Select a set-point temperature that is more than two degrees above the room temperature to call for the second stage of heating. The electric heat should energize along with the 24v compressor signal between “Y” and “C”. Check to see that the amp draw corresponds with the electric heat rating.

The following current values apply when the unit is connected to a 230V power supply. These values include indoor fan mo- tor current. If the supply power is different, this will affect the amp draw of the heater.

5kw = 22.3 amps, 4kw = 18 amps,

3kw = 13.5 amps.

Units with electric heat utilize a control relay located on the circuit board in the control box. As a safety feature, an auto resetting limit switch located on the heater end plate or on the heater assembly will interrupt power to the heater should an over- heat condition occur. Each electric heat assembly is also equipped with a one time fuse link. Should electric heat temperatures rise above the auto resetting limit switch, a non-resetting, one time fuse link will open and the heater will remain off (to restart a new fuse link is required).

Units with Condensation Pumps

EMI Air Handlers are available with an optional condensate pump. Condensate pumps are recommended when it is not possible to gravity drain the condensation from the indoor unit. Depending on the pump manufacture the maximum lift for the pump will vary. Consult the pump instruc- tions for the maximum lift for the particular pump being used.

Condensation generated by the evapo- rator will collect in the pumps’ reservoir. When the water level is high enough, a float switch will close and energize the pump motor clearing the water from the reservoir. Should for any reason the water exceed the maximum preset level, a safety switch will open, there by interrupting the (Y) signal to the condenser. This will prevent the evapo- rator from generating more condensation and spilling out of the unit.

WLCA/WLHA High Wall Evaporator

32

www.enviromaster.com

Image 32
Contents Installation, operation and maintenance Manual To the Installer Safety Instructions Day programmable with copy feature Product DescriptionControls and Components Anti-Short Cycle Compressor Pro- tectionCabinet Features Installer Supplied ItemsWLCA/WLHA Controls and Components Optional EquipmentWLCA/WLHA Mounting preparation WLCA/WLHA High Wall unit MountingWLCA/WLHA High Wall Evaporator Installation Instructions Electrical Wiring Site PreparationMake sure power is off Locate Electrical WiringHigh Volt Electrical Wiring Low Volt Interconnect wiringWiring must be at least 18 awg Units With or without heatStraight Cool Choosing a Remote Wall MountedHeat pump connection Remote thermostat Two-stage Heating Refrigerant Piping Piping Do’s and Don’tsPiston/Orifice Installation Instruction WLH24Manifold Setup For Evacuation Charge to proper weight, charge WLCA/WLHA High Wall Evaporator Quick Guide Configuration Mode User interface ButtonsControl User Interface instructions User interface Buttons Mode of operation On/OffFan Operation Louver operationSequence of Operation Unit Mounted key pad mode Cool ModeHeat Mode Optional Heat pump with Electric heat 2-stage heatingDry Mode Set Time ModeDay Programming mode Pre-programmed run modeManual run Filter CheckRoom Air Sampling Configuration Mode Min, 10 min, and 15 minChoosing a Thermostat Sleep timerSequence of Operation Wall mounted thermostat mode Cooling operation Electric heat operationOther Features Short Cycle Protection AsctLCD Back Light Drain Pan SensorMemory Backup Room air sensor fault E01Condensate fault E02 ID coil sensor fault E03WLCA/WLHA Preperation for Start-Up Optional Hand Held Controller programmingInitial Start-up Test Unit Performance Data sheet Test Unit Performance DataMaintenance and Troubleshooting procedure MaintenanceTroubleshooting EMI Air handlers with Unit Mount Infrared ControlsTroubleshooting procedure Power supply checkLow volt controls Cooling Only UnitsElectric Heat Optional Heat pump With Electric HeatUnits with Condensation Pumps Frequently asked questions Display on the indoor unit is blank What should I do?Troubleshooting procedure WLCA/WLHA Physical Dimensions Mounting Tubing Model Depth Height LengthWLCA/WLHA High Wall Evaporator Specifications WLCA/WLHA Electrical SpecificationsSmall Cabinet 09/12 Medium Cabinet 18/24WLCA/WLHA System Options Cooling Systems with Wall UnitsHeat pumps System Options with Wall Units Cooling Systems with S2CA Side dischargeSystem Options with T2CA TOP discharge System Options with T3CA TOP dischargeALL Product Limited Warranty EMI’s High Efficiency Product Line EvaporatorsHigh Wall Evaporator Condensers

WLHA, S1C specifications

The EMI S1C, also known as the WLHA, is a cutting-edge electronic device renowned for its advanced features and robust technologies. This innovative equipment caters to a wide range of applications, from multimedia processing to advanced communications. Its design showcases a seamless blend of functionality and performance, making it a preferred choice among professionals in various fields.

One of the standout characteristics of the EMI S1C is its high-performance processing capability. Equipped with a powerful multi-core processor, the device ensures rapid data processing and multitasking without compromising efficiency. This feature is particularly beneficial for applications requiring real-time data analysis and complex computational tasks.

The WLHA further distinguishes itself through its exceptional connectivity options. It supports multiple input and output standards, including USB, HDMI, and Ethernet, facilitating seamless integration with other devices. This flexibility allows users to connect a variety of peripherals and streamline workflows, enhancing overall productivity.

In terms of user experience, the EMI S1C places a strong emphasis on intuitive interaction. It features a user-friendly interface that simplifies navigation and accessibility. The touchscreen display provides responsive feedback, enabling users to operate the device effortlessly, even in high-pressure scenarios.

Another prominent aspect of the EMI S1C is its advanced power management system. The device is designed to optimize energy consumption without sacrificing performance. This sustainability feature is not only environmentally friendly but also crucial for mobile applications, where battery life is a significant consideration.

Furthermore, the WLHA's robust build quality ensures durability and resilience in diverse environments. The device is constructed with high-grade materials that withstand wear and tear, making it ideal for use in industrial settings or field operations where ruggedness is essential.

Security is also at the forefront of the EMI S1C's design. The device incorporates advanced encryption technologies and secure boot mechanisms to protect sensitive data from unauthorized access. This commitment to security is particularly relevant in today's digital landscape, where data breaches and cyber threats are prevalent.

In summary, the EMI S1C, WLHA is a versatile and powerful electronic device that excels in various domains. Its combination of high-performance processing, extensive connectivity, user-friendly interface, energy efficiency, durability, and robust security features makes it a top choice for professionals seeking reliability and innovation in their tools. Whether in multimedia, telecommunications, or industrial applications, the WLHA is poised to meet the demands of modern technology users effectively.