WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Specifications” on pages 3, 4 and 5.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.

The electrical specifications list fuse and wire sizes (75°F copper) for all models including the most commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.

WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 9.

TABLE 9

THERMOSTAT WIRE SIZE

 

 

 

Maximum

 

 

 

Distance

Transformer VA

FLA

Wire Gauge

In Feet

 

 

20

45

 

 

18

60

55

2.3

16

100

 

 

14

160

 

 

12

250

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

THERMOSTATS

See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring diagrams..

TABLE 10

WALL THERMOSTAT AND SUBBASE COMBINATIONS

Thermostat

Subbase

 

Predominant Features

 

 

 

 

8403-022

8403-003

1 stage heat, 1 stage cool,

Mercury

T87F3111

Q539A1220

System: Heat-off-cool

Fan: on-auto

8403-041

——

1 stage heat, 1 stage cool,

Mercury

T8034C1499

System: Heat-off-cool

Fan: on-auto

 

8403-049

——

2 stage heat, 2 stage cool,

 

1F93-380

Electronic

Programmable

 

 

 

8403-043

——

1 stage heat, 1 stage cool,

Mercury

CM200

System: Heat-off-cool

Fan: on-auto Snap Action

 

8403-048

 

1 stage heat, 1 stage cool,

Mercury

——

System: Heat-off-cool

Fan: on-auto

T8400C1313

 

Electronic

Non-Programmable

 

 

8403-019

8404-012

1 stage heat, 1 stage cool,

Mercury

T874C1760

Q674C1760

System: Heat-auto-cool

Fan: on-auto

IMPORTANT NOTE: Only the thermostat and subbase combinations as shown above will work with this equipment. The thermostat and subbase MUST be matched, and correct operation can be assured only by proper selection and application of these parts.

Manual 2100-353

Page 15

Image 17
Contents Installation Instructions Single Package AIR Conditioners Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Instructions Field Installed Heater Packages OptionalShipping Damage GeneralHz Circuit a Electrical SpecificationsCompressor Circuit a Fan Motor and Condenser414 12.8 Volts Model Phase Heater Package Volts Model PhaseP1236A1-B This columnHtr. KW Circuit B Capacity @ 240 Volts @ 208 Volts Optional Field Installed Electric Heater TableHtr. Amps Fuses Circuits Ampacity Protection SizeDimensions of Units Location InstallationTypical Installations Slab Mounting AT Ground Level Airflow and Service Access ClearancesElevated Mounting Platforms Roof TOP ApplicationMIS-1177C Unit Model Roof Hood Dimension Dimension for X in FIGRoof Curb Details Field Fabricated CurbingAIR Filters Condensate Drain TrapFilter Requirements & Sizes Condensate Drain TrapWiring 24V LOW Voltage Control Circuit Wiring Main PowerTransformer Taps ThermostatsLOW Voltage Wiring Start UP and Operation LOW Pressure SWITCH, BYPASS, and Lockout Sequence AdjustmentsAlarm Output Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK TimerService Hints Service and TroubleshootingPressure Service Ports FAN Blade SettingsSuction and Discharge Tube Brazing Brazing DiagramIndoor Blower Perfomance ESP P1124A2 P1130A2 P1136A2 P1142A3 P1148A2 P1060A1Return Air Pressure 100 105 110 115 Model Pressure TablePressure Table Motor rocks slightly when starting Motor wont start Troubleshooting ECM Blower Motors∃ Run Mositure Check Evidence of Moisture∃ Perform Moisture Check Motor starts but runs erraticallyExcessive noise

P1230A1, P1124A2, P1148A2, P1236A1, P1248A2 specifications

The Bard P1136A2, P1242A1, P1130A2, P1224A1, and P1248A2 are high-performance industrial filtration systems renowned for their efficiency and advanced technologies. Ideal for various applications, including air, water, and process fluid filtration, these systems have become essential tools in a multitude of industries.

The Bard P1136A2 features a robust design that emphasizes durability and reliability. Equipped with high-efficiency particulate air (HEPA) filters, it substantially reduces airborne contaminants, making it suitable for cleanroom environments and laboratories. Its advanced monitoring system alerts users when filters need replacing, ensuring optimal performance at all times. The P1136A2 is also designed for easy maintenance, allowing quick access to components without extensive downtime.

Similarly, the Bard P1242A1 offers a distinctive combination of high filtration efficiency and low operational costs. Its multi-stage filtration process employs activated carbon to remove volatile organic compounds (VOCs) and odors. This system is particularly beneficial in industrial settings where air quality is paramount. The P1242A1 is designed with energy-saving technology, resulting in lower energy consumption without compromising filtration performance.

The Bard P1130A2 stands out with its compact design, making it an ideal choice for facilities with limited space. Despite its size, it delivers powerful filtration capabilities, utilizing an advanced pleated filter technology that maximizes surface area while minimizing resistance. This feature ensures long filter life and reduces maintenance frequency, translating to cost savings for end-users.

The Bard P1224A1 is characterized by its versatile applications and ease of integration with existing systems. Its modular design allows customization based on specific industrial requirements, making it suitable for diverse environments. Incorporating smart technology, the P1224A1 provides real-time monitoring and analytics, enabling proactive maintenance and enhancing operational efficiency.

Lastly, the Bard P1248A2 showcases cutting-edge design focusing on sustainability. Its energy-efficient components are coupled with eco-friendly materials, reducing the carbon footprint associated with filtration processes. This system is designed for industries aiming for compliance with environmental regulations while maintaining high performance and reliability.

Collectively, these Bard filtration systems epitomize technological advancement, offering unique features tailored to meet modern industrial challenges. Their focus on efficiency, sustainability, and user-friendly designs positions them as leaders in the filtration market, ensuring cleaner environments for all applications.