Bard P1148A2, P1248A2, P1230A1 Service and Troubleshooting, Service Hints, Pressure Service Ports

Page 21

SERVICE AND TROUBLESHOOTING

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.

2.Check all power fuses or circuit breakers to be sure that they are the correct rating.

3.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in this manual covering all models on cooling cycle. It is imperative to match the correct pressure table to the unit by model number.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 11.

TABLE 11

SUCTION LINE TEMPERATURES

 

Rated

95° OD

82° OD

Model

Airflow

Temperature

Temperature

 

 

 

 

P1124A2

800

56 - 58

63 - 65

 

 

 

 

P1224A1

800

56 - 58

63 - 65

P1130A2

1125

56 - 58

63 - 65

 

 

 

 

P1230A1

1000

56 - 58

63 - 65

P1136A2

1250

57 - 59

58 - 60

 

 

 

 

P1236A1

1100

57 - 59

58 - 60

P1142A3

1400

57 - 59

58 - 60

 

 

 

 

P1242A1

1400

57 - 59

58 - 60

P1148A2

1550

54 - 57

58 - 60

 

 

 

 

P1248A2

1550

53 - 55

56 - 58

P1060A1

1700

47 - 49

54 - 56

 

 

 

 

The above suction line temperatures are based upon 80°F dry bulb/67°F wet bulb (50% RH) temperature and rated airflow across the evaporator during cooling cycle.

FAN BLADE SETTINGS

Shown in Figure 10 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 10

FAN BLADE SETTING

TABLE 12

FAN BLADE SETTING DIMENSIONS

Model

Dimension "A"

 

 

P1124A2

1.00"

 

 

P1224A1

1.00"

P1130A2

.75"

 

 

P1230A1

1.00"

P1136A2

1.00"

 

 

P1236A1

1.00"

P1142A3

1.75"

 

 

P1242A1

1.75"

P1148A2

1.75"

 

 

P1248A2

1.75"

 

 

P1060A1

1.75"

 

 

Manual 2100-353 Page 19

Image 21
Contents Installation Instructions Single Package AIR Conditioners Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Instructions Field Installed Heater Packages OptionalShipping Damage GeneralHz Circuit a Electrical SpecificationsCompressor Circuit a Fan Motor and Condenser414 12.8 Volts Model Phase Heater Package Volts Model PhaseP1236A1-B This columnHtr. KW Circuit B Capacity @ 240 Volts @ 208 Volts Optional Field Installed Electric Heater TableHtr. Amps Fuses Circuits Ampacity Protection SizeDimensions of Units Installation Typical InstallationsLocation Slab Mounting AT Ground Level Airflow and Service Access ClearancesElevated Mounting Platforms Roof TOP ApplicationMIS-1177C Unit Model Roof Hood Dimension Dimension for X in FIGRoof Curb Details Field Fabricated CurbingAIR Filters Condensate Drain TrapFilter Requirements & Sizes Condensate Drain TrapWiring 24V LOW Voltage Control Circuit Wiring Main PowerTransformer Taps ThermostatsLOW Voltage Wiring Start UP and Operation LOW Pressure SWITCH, BYPASS, and Lockout Sequence AdjustmentsAlarm Output Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK TimerService Hints Service and TroubleshootingPressure Service Ports FAN Blade SettingsSuction and Discharge Tube Brazing Brazing DiagramIndoor Blower Perfomance ESP P1124A2 P1130A2 P1136A2 P1142A3 P1148A2 P1060A1Return Air Pressure 100 105 110 115 Model Pressure TablePressure Table Motor rocks slightly when starting Motor wont start Troubleshooting ECM Blower Motors∃ Run Mositure Check Evidence of MoistureMotor starts but runs erratically Excessive noise∃ Perform Moisture Check

P1230A1, P1124A2, P1148A2, P1236A1, P1248A2 specifications

The Bard P1136A2, P1242A1, P1130A2, P1224A1, and P1248A2 are high-performance industrial filtration systems renowned for their efficiency and advanced technologies. Ideal for various applications, including air, water, and process fluid filtration, these systems have become essential tools in a multitude of industries.

The Bard P1136A2 features a robust design that emphasizes durability and reliability. Equipped with high-efficiency particulate air (HEPA) filters, it substantially reduces airborne contaminants, making it suitable for cleanroom environments and laboratories. Its advanced monitoring system alerts users when filters need replacing, ensuring optimal performance at all times. The P1136A2 is also designed for easy maintenance, allowing quick access to components without extensive downtime.

Similarly, the Bard P1242A1 offers a distinctive combination of high filtration efficiency and low operational costs. Its multi-stage filtration process employs activated carbon to remove volatile organic compounds (VOCs) and odors. This system is particularly beneficial in industrial settings where air quality is paramount. The P1242A1 is designed with energy-saving technology, resulting in lower energy consumption without compromising filtration performance.

The Bard P1130A2 stands out with its compact design, making it an ideal choice for facilities with limited space. Despite its size, it delivers powerful filtration capabilities, utilizing an advanced pleated filter technology that maximizes surface area while minimizing resistance. This feature ensures long filter life and reduces maintenance frequency, translating to cost savings for end-users.

The Bard P1224A1 is characterized by its versatile applications and ease of integration with existing systems. Its modular design allows customization based on specific industrial requirements, making it suitable for diverse environments. Incorporating smart technology, the P1224A1 provides real-time monitoring and analytics, enabling proactive maintenance and enhancing operational efficiency.

Lastly, the Bard P1248A2 showcases cutting-edge design focusing on sustainability. Its energy-efficient components are coupled with eco-friendly materials, reducing the carbon footprint associated with filtration processes. This system is designed for industries aiming for compliance with environmental regulations while maintaining high performance and reliability.

Collectively, these Bard filtration systems epitomize technological advancement, offering unique features tailored to meet modern industrial challenges. Their focus on efficiency, sustainability, and user-friendly designs positions them as leaders in the filtration market, ensuring cleaner environments for all applications.