Bard P1230A1, P1248A2, P1236A1, P1148A2, P1242A1, P1136A2, P1130A2, P1224A1 Start UP and Operation

Page 19

START UP AND OPERATION

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.

Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation for several minutes the compressor’s internal protector will trip.

All three phase ZR*3 compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminals should maintain proper rotation direction.

The direction of rotation of the motor may be changed by reversing any two line connections to the unit.

SEQUENCE OF OPERATION

COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation, or can be energized by manual fan switch on subbase for constant air circulation.

HEATING – A circuit R-W1 is completed on each heating cycle energizing electric heat if so equipped.

START UP NOTES

For improved start up performance, wash the indoor coil with dishwasher detergent.

INDOOR BLOWER MOTOR

Some models feature a variable speed (ECM) motor providing high efficiency, low sound levels and soft start capabilities. The motor is self adjusting to provide the proper air flow rate at duct static pressures up to 0.50” WC without user adjustment or wiring changes.

On command from the wall thermostat the motor will start slowly and ramp up to full speed over a period of 10- 15 seconds.

When the thermostat is satisfied the blower will operate for approximately 1 minute, and then slow down and stop.

COMPRESSOR CONTROL MODULE

The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm output.

ADJUSTABLE DELAY-ON-MAKE AND BREAK TIMER

On a call for compressor operation the delay-on-makeperiod begins which will be 10% of the delay-on-breaksetting. When the delay-on-make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay-on-break timer starts and prevents restart until the delay-on-break and delay-on-make periods have expired.

HIGH PRESSURE SWITCH AND LOCKOUT SEQUENCE (Standard Feature)

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay-on- make time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm circuit will energize. Recycling the wall thermostat resets the manual lockout.

Manual 2100-353 Page 17

Image 19
Contents Installation Instructions Single Package AIR Conditioners Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Field Installed Heater Packages OptionalGeneral Instructions Shipping DamageFan Motor and Condenser Electrical SpecificationsHz Circuit a Compressor Circuit a414 12.8 This column Heater Package Volts Model PhaseVolts Model Phase P1236A1-BSize Optional Field Installed Electric Heater TableHtr. KW Circuit B Capacity @ 240 Volts @ 208 Volts Htr. Amps Fuses Circuits Ampacity ProtectionDimensions of Units Typical Installations InstallationLocation Slab Mounting AT Ground Level Airflow and Service Access ClearancesElevated Mounting Platforms Roof TOP ApplicationMIS-1177C Field Fabricated Curbing Dimension for X in FIGUnit Model Roof Hood Dimension Roof Curb DetailsCondensate Drain Trap Condensate Drain TrapAIR Filters Filter Requirements & SizesThermostats Wiring Main PowerWiring 24V LOW Voltage Control Circuit Transformer TapsLOW Voltage Wiring Start UP and Operation Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer AdjustmentsLOW Pressure SWITCH, BYPASS, and Lockout Sequence Alarm OutputFAN Blade Settings Service and TroubleshootingService Hints Pressure Service PortsESP P1124A2 P1130A2 P1136A2 P1142A3 P1148A2 P1060A1 Brazing DiagramSuction and Discharge Tube Brazing Indoor Blower PerfomanceReturn Air Pressure 100 105 110 115 Model Pressure TablePressure Table Evidence of Moisture Troubleshooting ECM Blower MotorsMotor rocks slightly when starting Motor wont start ∃ Run Mositure CheckExcessive noise Motor starts but runs erratically∃ Perform Moisture Check

P1230A1, P1124A2, P1148A2, P1236A1, P1248A2 specifications

The Bard P1136A2, P1242A1, P1130A2, P1224A1, and P1248A2 are high-performance industrial filtration systems renowned for their efficiency and advanced technologies. Ideal for various applications, including air, water, and process fluid filtration, these systems have become essential tools in a multitude of industries.

The Bard P1136A2 features a robust design that emphasizes durability and reliability. Equipped with high-efficiency particulate air (HEPA) filters, it substantially reduces airborne contaminants, making it suitable for cleanroom environments and laboratories. Its advanced monitoring system alerts users when filters need replacing, ensuring optimal performance at all times. The P1136A2 is also designed for easy maintenance, allowing quick access to components without extensive downtime.

Similarly, the Bard P1242A1 offers a distinctive combination of high filtration efficiency and low operational costs. Its multi-stage filtration process employs activated carbon to remove volatile organic compounds (VOCs) and odors. This system is particularly beneficial in industrial settings where air quality is paramount. The P1242A1 is designed with energy-saving technology, resulting in lower energy consumption without compromising filtration performance.

The Bard P1130A2 stands out with its compact design, making it an ideal choice for facilities with limited space. Despite its size, it delivers powerful filtration capabilities, utilizing an advanced pleated filter technology that maximizes surface area while minimizing resistance. This feature ensures long filter life and reduces maintenance frequency, translating to cost savings for end-users.

The Bard P1224A1 is characterized by its versatile applications and ease of integration with existing systems. Its modular design allows customization based on specific industrial requirements, making it suitable for diverse environments. Incorporating smart technology, the P1224A1 provides real-time monitoring and analytics, enabling proactive maintenance and enhancing operational efficiency.

Lastly, the Bard P1248A2 showcases cutting-edge design focusing on sustainability. Its energy-efficient components are coupled with eco-friendly materials, reducing the carbon footprint associated with filtration processes. This system is designed for industries aiming for compliance with environmental regulations while maintaining high performance and reliability.

Collectively, these Bard filtration systems epitomize technological advancement, offering unique features tailored to meet modern industrial challenges. Their focus on efficiency, sustainability, and user-friendly designs positions them as leaders in the filtration market, ensuring cleaner environments for all applications.