Bard MIS-656 installation instructions Compressor Control Module, Pressure Service Ports

Page 16

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the models covered by this manual. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10% of the delay on break setting.

When the delay on make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired.

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5minute (30 seconds) DOB = 123 second DOM

1.0minute (60 seconds) DOB = 126 second DOM

2.0minute (120 seconds) DOB = 132 second DOM

3.0minute (180 seconds) DOB = 138 second DOM

4.0minute (240 seconds) DOB = 144 second DOM

5.0minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

Manual 2100-404 Page 14

Image 16
Contents WA372 Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersWall Mount General Information Electrical SpecificationsAIR Conditioner Wall Mount Model Nomenclature Dimensions of Basic Unit Nominal Back ViewGeneral Shipping DamageElectric Heat Table Fresh AIR Damper Assembly Duct WorkFresh AIR Intake Condensate DrainInstallation Instructions Wiring Main PowerWall Mounting Information Mounting the UnitWiring LOW Voltage Wiring Thermostat Wire SizeOperating Voltage Range Wall Thermostat and Subbase CombinationsMounting Instructions WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Electric Heat Clearance LOW Voltage Wiring Start UP Pressure Service Ports Compressor Control ModuleTroubleshooting FAN Blade Setting DimensionsRemoval of FAN Shroud Refrigerant ChargeOutdoor Temperature F Cooling PressureOptional Accessories WA302-A WA372-A WA302-B WA372-B

MIS-656 specifications

The Bard MIS-656 is a state-of-the-art medical device designed for optimal performance in a variety of clinical settings. Specifically engineered for minimally invasive surgical procedures, the MIS-656 offers surgeons a range of advanced features that enhance precision, efficiency, and patient safety.

One of the standout characteristics of the Bard MIS-656 is its innovative imaging technology. It utilizes high-definition visualization that provides surgeons with clear and detailed images of the surgical field. This enables better identification of anatomical structures, reducing the risk of complications during procedures. The device also integrates advanced optics, allowing for an expanded field of view, which is crucial in minimally invasive surgeries.

In terms of ergonomics, the MIS-656 is crafted with the surgeon's comfort in mind. The device features a lightweight design that minimizes strain during extended operations. Its intuitive controls and adaptable design ensure that surgeons can easily maneuver the device, leading to reduced fatigue and increased focus on patient outcomes.

Another major advantage of the Bard MIS-656 is its versatility. The device is compatible with a range of surgical instruments, making it suitable for diverse surgical specialties, including gynecology, urology, and general surgery. This multi-functional capability allows hospitals to optimize their surgical instruments and improve overall operating room efficiency.

The MIS-656 also integrates seamlessly with digital documentation systems. This connectivity allows for real-time data capture and monitoring, facilitating better communication between surgical teams. Enhanced data tracking contributes to improved patient care and outcomes, as medical professionals can analyze trends and adapt procedures accordingly.

Safety is a paramount concern in surgical environments, and the Bard MIS-656 is equipped with features designed to minimize risks. Its robust design and advanced materials ensure durability, while safety mechanisms, such as failsafe locking systems, enhance operational reliability.

In summary, the Bard MIS-656 exemplifies innovation in minimally invasive surgical technology. With superior imaging capabilities, ergonomic design, surgical versatility, and commitment to safety, this device stands out as a valuable addition to modern operating rooms. As surgical techniques continue to evolve, the MIS-656 positions itself as a key asset for healthcare providers seeking to enhance surgical precision and patient care.