Bard MIS-656 installation instructions Start UP

Page 15

START UP

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil with a dishwasher detergent.

HIGH PRESSURE SWITCH

The WA372 models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on again.

THREE PHASE SCROLL COMPRESSOR START UP INFORMATION

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.

However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. All three phase units incorporate a phase monitor to ensure proper field wiring. See the Phase Monitor section later in this manual.

Verification of proper rotation must be made any time a compressor is change or rewired. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation for several minutes, the compressor's internal protector will trip.

All three phase ZR3 compressors are wired identical internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction.

Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized.

Reverse rotation also results in an elevated sound level over that with correct rotations, as well as, substantially reduced current draw compared to tabulated values.

The direction of rotation of the compressor may be changed by reversing any two line connections to the unit.

PHASE MONITOR

All units with three phase compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

SERVICE HINTS

1.Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs.

2.Check all power fuses or circuit breakers to be sure they are the correct rating.

3.Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On all 230 volt units there is a one minute off delay on the blower motor. 460 volt models do not have an off delay. On a call for heating, circuit R-W1 make at the thermostat pulling in heat contact for the strip heat and blower operation. On a call for second stage heat, R-W2 makes bringing on second heat contactor, if so equipped.

Manual 2100-404 Page 13

Image 15
Contents WA372 Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsElectrical Specifications Wall Mount General InformationAIR Conditioner Wall Mount Model Nomenclature Back View Dimensions of Basic Unit NominalShipping Damage GeneralElectric Heat Table Condensate Drain Fresh AIR Damper AssemblyDuct Work Fresh AIR IntakeMounting the Unit Installation InstructionsWiring Main Power Wall Mounting InformationWall Thermostat and Subbase Combinations Wiring LOW Voltage WiringThermostat Wire Size Operating Voltage RangeMounting Instructions WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Electric Heat Clearance LOW Voltage Wiring Start UP Compressor Control Module Pressure Service PortsRefrigerant Charge TroubleshootingFAN Blade Setting Dimensions Removal of FAN ShroudCooling Pressure Outdoor Temperature FWA302-A WA372-A WA302-B WA372-B Optional Accessories

MIS-656 specifications

The Bard MIS-656 is a state-of-the-art medical device designed for optimal performance in a variety of clinical settings. Specifically engineered for minimally invasive surgical procedures, the MIS-656 offers surgeons a range of advanced features that enhance precision, efficiency, and patient safety.

One of the standout characteristics of the Bard MIS-656 is its innovative imaging technology. It utilizes high-definition visualization that provides surgeons with clear and detailed images of the surgical field. This enables better identification of anatomical structures, reducing the risk of complications during procedures. The device also integrates advanced optics, allowing for an expanded field of view, which is crucial in minimally invasive surgeries.

In terms of ergonomics, the MIS-656 is crafted with the surgeon's comfort in mind. The device features a lightweight design that minimizes strain during extended operations. Its intuitive controls and adaptable design ensure that surgeons can easily maneuver the device, leading to reduced fatigue and increased focus on patient outcomes.

Another major advantage of the Bard MIS-656 is its versatility. The device is compatible with a range of surgical instruments, making it suitable for diverse surgical specialties, including gynecology, urology, and general surgery. This multi-functional capability allows hospitals to optimize their surgical instruments and improve overall operating room efficiency.

The MIS-656 also integrates seamlessly with digital documentation systems. This connectivity allows for real-time data capture and monitoring, facilitating better communication between surgical teams. Enhanced data tracking contributes to improved patient care and outcomes, as medical professionals can analyze trends and adapt procedures accordingly.

Safety is a paramount concern in surgical environments, and the Bard MIS-656 is equipped with features designed to minimize risks. Its robust design and advanced materials ensure durability, while safety mechanisms, such as failsafe locking systems, enhance operational reliability.

In summary, the Bard MIS-656 exemplifies innovation in minimally invasive surgical technology. With superior imaging capabilities, ergonomic design, surgical versatility, and commitment to safety, this device stands out as a valuable addition to modern operating rooms. As surgical techniques continue to evolve, the MIS-656 positions itself as a key asset for healthcare providers seeking to enhance surgical precision and patient care.