Bard MIS-656 Installation Instructions, Wall Mounting Information, Mounting the Unit

Page 8

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.

2.On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

WARNING

Fire hazard can result if 1/4 inch clearance to combustible materials for supply air duct is not maintained. See Figure 3.

3.Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit.

MOUNTING THE UNIT

1.These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but is not required.

2.The unit itself is suitable for “0” inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 28-1/2" x 8-1/2" dimensions for sizing. However, it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire.

3.Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.

4.Mount bottom mounting bracket, if used The supply air opening would then be 30" x 10". See Figures 3 and 4 for details.

5.Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.

6.Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7.Secure rain flashing to wall and caulk across entire length of top. See Figure 3.

8.For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance of combustible wall.

9.On side by side installations, maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

TOP OUTLET ONLY

1.Remove airframe angles from the back of the unit.

2.Coat angles with two 1/8" beads of silicone as shown. Silicone is shipped in the control panel. See Figure 5.

3.Secure angles to the top of the unit with 14 screws provided. Use of prepunched holes provided. Do not relocate. See Figure 5.

4.After installation duct work, seal around airframe and duct work to provide a rain tight seal.

5.It is strongly recommended, but not required, that this unit be installed under a soffit area large enough to shield the top of the unit. See Figure 6.

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

Manual 2100-404 Page 6

Image 8
Contents WA372 Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersAIR Conditioner Wall Mount Model Nomenclature Electrical SpecificationsWall Mount General Information Dimensions of Basic Unit Nominal Back ViewElectric Heat Table Shipping DamageGeneral Fresh AIR Damper Assembly Duct WorkFresh AIR Intake Condensate DrainInstallation Instructions Wiring Main PowerWall Mounting Information Mounting the UnitWiring LOW Voltage Wiring Thermostat Wire SizeOperating Voltage Range Wall Thermostat and Subbase CombinationsMounting Instructions WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Electric Heat Clearance LOW Voltage Wiring Start UP Pressure Service Ports Compressor Control ModuleTroubleshooting FAN Blade Setting DimensionsRemoval of FAN Shroud Refrigerant ChargeOutdoor Temperature F Cooling PressureOptional Accessories WA302-A WA372-A WA302-B WA372-B

MIS-656 specifications

The Bard MIS-656 is a state-of-the-art medical device designed for optimal performance in a variety of clinical settings. Specifically engineered for minimally invasive surgical procedures, the MIS-656 offers surgeons a range of advanced features that enhance precision, efficiency, and patient safety.

One of the standout characteristics of the Bard MIS-656 is its innovative imaging technology. It utilizes high-definition visualization that provides surgeons with clear and detailed images of the surgical field. This enables better identification of anatomical structures, reducing the risk of complications during procedures. The device also integrates advanced optics, allowing for an expanded field of view, which is crucial in minimally invasive surgeries.

In terms of ergonomics, the MIS-656 is crafted with the surgeon's comfort in mind. The device features a lightweight design that minimizes strain during extended operations. Its intuitive controls and adaptable design ensure that surgeons can easily maneuver the device, leading to reduced fatigue and increased focus on patient outcomes.

Another major advantage of the Bard MIS-656 is its versatility. The device is compatible with a range of surgical instruments, making it suitable for diverse surgical specialties, including gynecology, urology, and general surgery. This multi-functional capability allows hospitals to optimize their surgical instruments and improve overall operating room efficiency.

The MIS-656 also integrates seamlessly with digital documentation systems. This connectivity allows for real-time data capture and monitoring, facilitating better communication between surgical teams. Enhanced data tracking contributes to improved patient care and outcomes, as medical professionals can analyze trends and adapt procedures accordingly.

Safety is a paramount concern in surgical environments, and the Bard MIS-656 is equipped with features designed to minimize risks. Its robust design and advanced materials ensure durability, while safety mechanisms, such as failsafe locking systems, enhance operational reliability.

In summary, the Bard MIS-656 exemplifies innovation in minimally invasive surgical technology. With superior imaging capabilities, ergonomic design, surgical versatility, and commitment to safety, this device stands out as a valuable addition to modern operating rooms. As surgical techniques continue to evolve, the MIS-656 positions itself as a key asset for healthcare providers seeking to enhance surgical precision and patient care.