Indoor Blower Performance - CFM at Rated Volts
ESP | W17A1 | W24A1 | W30A1 | W42A1 | W60A1 | |||||
W18A1 | W36A1 | W48A1 | ||||||||
|
|
| ||||||||
in |
|
|
|
|
|
|
|
|
| |
H2O | High Speed | Low Speed | Single Speed | High Speed | Low Speed | High Speed | Low Speed | High Speed | Low Speed | |
| Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | Dry/Wet Coil | |
|
|
|
|
|
|
|
|
|
| |
0 | 925/885 | 670/655 | 1020/975 | 1395/1315 | 950/935 | 1885/1800 | 1650/1600 | 2200/2000 | 1600/1450 | |
|
|
|
|
|
|
|
|
|
| |
.1 | 875/845 | 650/630 | 960/905 | 1340/1270 | 930/915 | 1770/1665 | 1550/1500 | 2100/1900 | 1525/1375 | |
|
|
|
|
|
|
|
|
|
| |
.2 | 825/795 | 625/600 | 865/800 | 1285/1190 | 910/885 | 1635/1550 | 1450/1400 | 2000/1800 | 1465/1200 | |
|
|
|
|
|
|
|
|
|
| |
.3 | 775/740 | 575/555 | 820/735 | 1205/1100 | 855/830 | 1500/1400 | 1350/1300 | 1875/1700 | ||
|
|
|
|
|
|
|
|
|
| |
.4 | 710/670 | 525/500 | 735/650 | 1110/1000 | 800/755 | 1370/1285 | 1300/1175 | 1775/1600 | ||
|
|
|
|
|
|
|
|
|
| |
.5 | 635/600 | 465/440 | 615/535 | 1005/870 | 1250/1150 | 1650/1475 | ||||
|
|
|
|
|
|
|
|
|
|
Above data is with 1" standard throwaway filter and 1" washable filter. | Speeds marked “bold” above | |
For optional 2" pleated filter - reduce ESP by .15 in. | ||
are Factory Connected. | ||
See installation instructions for maximum ESP information on various KW application. | ||
|
Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
Nominal |
| At 240V (1) |
|
| At 208V (1) |
|
| At 480V (2) |
|
| At 460V (2) |
| ||
KW | Kw |
| Btuh | Kw | Btuh | Kw | Btuh | Kw | Btuh | |||||
| ||||||||||||||
5.0 | 5.0 | 20.8 |
| 17,065 | 3.75 | 18.0 |
| 12,799 |
|
|
|
|
|
|
6.0 | 6.0 |
| 14.4 | 20,478 | 4.50 |
| 12.5 | 15,359 | 6.0 | 7.2 | 20,478 | 5.52 | 6.9 | 18,840 |
8.0 | 8.0 | 33.3 |
| 27,304 | 6.00 | 28.8 |
| 20,478 |
|
|
|
|
|
|
9.0 | 9.0 |
| 21.7 | 30,717 | 6.75 |
| 18.7 | 23,038 | 9.0 | 10.8 | 30,717 | 8.28 | 10.4 | 28,260 |
10.0 | 10.0 | 41.7 |
| 34,130 | 7.50 | 36.1 |
| 25,598 |
|
|
|
|
|
|
15.0 | 15.0 | 62.5 | 36.1 | 51,195 | 11.25 | 54.1 | 31.2 | 38,396 | 15.0 | 18.0 | 51,195 | 13.80 | 17.3 | 47,099 |
18.0 | 18.0 |
| 43.3 | 61,434 | 13.50 |
| 37.5 | 46,076 | 18.0 | 21.7 | 61,434 | 16.56 | 20.8 | 56,519 |
20.0 | 20.0 | 83.3 |
| 68,260 | 15.00 | 72.1 |
| 51,195 |
|
|
|
|
|
|
(1)These electric heaters are available in 230/208V units only.
(2)These electric heaters are available in 480V units only.
Heater Packages - Field Installed
• Designed for adding Electric Heat to 0 KW Units |
| • ETL US & Canada Listed |
|
|
| ||
• Circuit Breaker Standard on 230/208V Models |
| • Toggle Disconnect Standard on 460V Models |
| ||||
Air Conditioner |
|
|
|
| |||
|
|
|
| ||||
Models |
|
|
|
| |||
Heater Model # | KW | Heater Model # |
| KW | Heater Model # | KW | |
|
| ||||||
W17A1 | 5 |
|
|
|
|
| |
8 | N/A |
| N/A |
| |||
W18A1 |
|
| |||||
10 |
|
|
|
|
| ||
|
|
|
|
|
| ||
| 5 |
|
|
|
|
| |
W24A1 | 8 |
| 6 | 6 | |||
| 10 |
|
|
|
|
| |
| 5 |
| 6 | 6 | |||
| 8 |
| |||||
W30A1 |
| 9 | 9 | ||||
10 |
| ||||||
|
| 15 | 15 | ||||
| 15 |
| |||||
|
|
|
|
|
| ||
| 5 |
| 6 | 6 | |||
| 8 |
| |||||
W36A1 |
| 9 | 9 | ||||
10 |
| ||||||
|
| 15 | 15 | ||||
| 15 |
| |||||
|
|
|
|
|
| ||
| 5 |
| 9 | 9 | |||
W42A1 | 10 |
| |||||
| 15 |
| 15 | ||||
W48A1 | 15 |
| |||||
| 18 |
|
| ||||
| 20 |
|
|
| |||
|
|
|
|
|
| ||
| 5 |
| 9 | 9 | |||
| 10 |
| |||||
W60A1 |
| 15 | 15 | ||||
15 |
| ||||||
|
| 18 |
|
| |||
| 20 |
|
|
| |||
|
|
|
|
|
|
NOTE: Field installed Heater Packages are not approved for use with top supply opening models.
1These heater packages approved for use in dehumidification versions with hot gas reheat.
Form No. | |
Supersedes | |
Page | 9 of 12 |