SPECIAL PROCEDURE IN THE CASE OF MOTOR COMPRESSOR BURNOUT

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation.

Failure to do so may result in personal injury, or death.

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could result in serious injury or death.

WARNING

EXPLOSION HAZARD

The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.

Failure to follow proper safety procedures result in serious injury or death.

1.Recover all refrigerant and oil from the system.

2.Remove compressor, capillary tube and filter drier from the system.

3.Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent. Use approved flushing agent to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary. Ensure all acid is neutralized.

4.Reassemble the system, including new drier strainer and capillary tube.

5.Proceed with step 8-10 on previous page.

ROTARY COMPRESSOR SPECIAL TROUBLESHOOTING AND SERVICE

Basically, troubleshooting and servicing rotary compres- sors is the same as on the reciprocating compressor with only one main exception:

NEVER, under any circumstances, liquid charge a rotary compressor through the LOW side. Doing so would cause permanent damage to the new compressor.

26

Image 27
Contents Volt EQ08M11A Volt XQ05M10A, XQ06M10A, XQ08M10A, XQ10M10ATable Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards Introduction00001 7th Digit Options 0 = Straight Cool6th Digit Voltage 5th DigitElectrical Ratings Performance DataFire Hazard Electric Shock HazardMake sure the wiring is adequate for your unit How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models Operating Sequence / Characteristics and Features Electronic Control Sequence of OperationSmart FAN Hermetic Components Functional Component DefinitionsMechanical Components Electrical ComponentsActivating Test Mode Components TestingTesting the Electronic Control Boards for XQ Models Error Code ListingsTest EQ08 System Control Switch TestEQ08 System Control Switch Test Thermostat AdjustmentFAN Motor CapacitorsCapacitor Check with Capacitor Analyzer Capacitor ConnectionsTesting the Heating Element Electric Shock Hazard Heating ElementDrain PAN Valve Refrigeration Sequence of Operation Refrigeration system under high pressure 410A Sealed System Repair ConsiderationsRisk of Electric Shock 410A Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableMethod Of Charging / Repairs Burn HazardFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Ground Test Single Phase Resistance TestExplosion Hazard Compressor ReplacementRecommended procedure for compressor replacement High TemperaturesRotary Compressor Special Troubleshooting and Service Routine Maintenance Sleeve / Drain Front CoverClearances Date Model Serial Room AIR Conditioner Unit Performance Test Data SheetProblem Possible Cause Possible Solution General Troubleshooting TipsGeneral Troubleshooting Tips Problem Possible Cause Action Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check Fused separately Problem Possible Cause Action Heat / Cool only Room AIR Conditioners Troubleshooting Tips Electronic Control Cool only Models Page Aham PUB. NO. RAC-1 Cooling Load Estimate Form Heat Gain from Quantity FactorsDAY Heat Load Form Following is an example using the heat load formInfiltration Windows & Doors AVG Windows & Doors Area, sq. ftRoom AIR Conditioners Limited Warranty Technical Support Contact Information Page Friedrich AIR Conditioning CO
Related manuals
Manual 32 pages 34.87 Kb Manual 16 pages 9.01 Kb Manual 32 pages 56.71 Kb Manual 87 pages 18.35 Kb

R-410A specifications

Friedrich R-410A is an advanced refrigerant widely used in HVAC (Heating, Ventilation, and Air Conditioning) systems, known for its high efficiency and environmental friendliness. As a hydrofluorocarbon (HFC) blend, R-410A has become the preferred alternative to R-22, which is being phased out due to its ozone-depleting potential. One of the main features of R-410A is its high latent heat of vaporization, which allows for efficient heat transfer and improved cooling performance in air conditioning units.

Technologically, R-410A operates at higher pressures than older refrigerants, meaning systems designed for R-410A need to be built with more robust components to safely handle these pressures. This results in a more compact system design that offers enhanced performance and reliability. The dual-component nature of R-410A—composed of difluoromethane (R-32) and pentafluoroethane (R-125)—provides an optimal balance of thermodynamic properties, leading to superior energy efficiency, especially in variable speed applications.

In terms of characteristics, R-410A has a higher cooling capacity, which enables HVAC systems to effectively cool larger spaces or run more efficiently when cooling smaller areas. The refrigerant is non-toxic and non-flammable, which enhances safety during its use. In addition, R-410A has a lower global warming potential relative to other refrigerants, making it a more environmentally responsible choice for modern cooling systems.

Moreover, R-410A systems typically require less refrigerant charge due to their efficiency, contributing to reduced greenhouse gas emissions. The adoption of R-410A aligns with regulatory trends aimed at minimizing the environmental impact of refrigerants in cooling applications.

Overall, the Friedrich R-410A refrigerant embodies a combination of technology and environmental stewardship, making it a cornerstone of contemporary HVAC design. Its ability to provide effective and energy-efficient cooling solutions while being compliant with modern environmental regulations positions R-410A as the refrigerant of choice for engineers and installers focused on sustainability and performance in air conditioning systems.