Lincoln Electric V200-T Safety Precautions, Routine Maintenance, Replacement of Internal Fuse

Page 20

D-1

MAINTENANCE

D-1

 

 

 

SAFETY PRECAUTIONS

WARNING

ELECTRIC SHOCK can kill.

• Have an electrician install and ser- vice this equipment.

Turn the input power off at the fuse box, disconnect supply lines and allow machine to sit for five minutes minimum to allow the power capaci- tors to discharge before working inside this equipment.

Do not touch electrically hot parts.

----------------------------------------------------------------------

INPUT FILTER CAPACITOR

DISCHARGE PROCEDURE

WARNING

The machine has internal capacitors which are charged to a high voltage during power-on conditions. This voltage is dangerous and must be discharged before the machine can be serviced. Discharging is done automatically by the machine each time the power is switched off. However, you must allow the machine to sit for at least 5 minutes to allow time for the process to take place.

------------------------------------------------------------------------

ROUTINE MAINTENANCE

1.Perform the following preventive maintenance procedures at least once every thousand hours of use. It is good practice to keep a preventive main- tenance record; a record tag attached to the machine works best.

2.Remove the machine cover (requires a 3 mm hex key) after allowing the minimum 5 minute power off requirement to let the input capacitors dis- charge.

WARNING

Failure to observe this discharge time requirement could result in severe electrical shock hazard.

------------------------------------------------------------------------

3.Keeping the machine clean will result in cooler operation and higher reliability. Be sure to clean the following areas with a low pressure air stream.

Printed circuit boards

Power switch

Fan blades

Louvers

Heat sink fins

Output terminals

4.Examine capacitors for leakage or oozing. If any leakage is noticed, take the unit to an authorized Lincoln Field Service Shop.

5.Examine the case for breakage. Repair or replace the case as required. Keep the case in good condition to ensure that high voltage parts are protected and correct spacings are main- tained.

6.Install machine covers and fasteners.

REPLACEMENT OF INTERNAL FUSE

The Invertec has additional protection provided to some circuits through an internal fuse. For replace- ment of that fuse proceed as follows:

1.Turn off the power to the unit and remove the input plug.

2.Allow the machine to stand for 5 minutes to let the input capacitors discharge.

3.Remove the machine cover.

4.Replace the blown fuse with a new 0.5A 500V slowblow fuse.

NOTE: If the fuse blows again after power is restored, the cause could be an internal breakdown in the power unit. In this case, take the unit to an authorized Lincoln Field Service Shop.

INVERTEC V200-T

Image 20
Contents Safety Depends on You InvertecSafety California Proposition 65 WarningsElectric Shock can kill Welding Sparks can cause fire or explosion IiiPrécautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Table of Contents Installation Technical Specifications V200T TIGSelect Suitable Location Electric Shock can killInput Connections Input Fuse and Supply WireOutput Connections Output Connection for Stick Welding Output and GAS Connection for TIG WeldingCylinder could explode if damaged General Description Safety InstructionsOperation Controls and Settings Figure B.1 Case Front ControlsOperation Welding in TIG Mode Remote Control OperationOperating Steps Sept97Welding in Stick Mode Set the Welding Process Switch to StickRecommended Electrode Amperage Ranges Invertec V200-T Smaw ProcessPulser Function Explanation of 2 Step and 4 Step ModesStep Cable Plugs AccessoriesOptional Accessories Maintenance Safety PrecautionsInput Filter Capacitor Discharge Procedure Routine MaintenanceTroubleshooting HOW to USE Troubleshooting GuideTroubleshooting Diagrams Invertec V200-T PartsInvertec V-200-T 308-A.1308-C 11-4-98308-C.1 Items Not ShownInvertec V-200-T How To Read Shop Drawings $700.00Precaucion Warnung