Lincoln Electric IM575 manual Routine and Period Maintenance

Page 13

5

MAINTENANCE

5

 

 

 

SAFETY PRECAUTIONS

Before servicing, read and observe all safety precautions throughout this manual.

WARNING

ELECTRIC SHOCK can kill.

Only qualified personnel should perform this maintenance.

Turn the input supply power OFF at the disconnect switch or fuse box before working on this

equipment.

Do not touch electrically hot parts.

• Allow resistance elements to cool before working near them.

Do not touch moving fan components.

------------------------------------------------------------------------

ROUTINE AND PERIOD

MAINTENANCE

DAILY

1.Remove any restrictions to airflow through the Load Bank.

2.Check the screens to make sure that no objects have blocked or entered the openings.

3.Verify that the airflow is in the proper direction.

4.Assure that there is no recirculation of the exhaust air through the Load Bank.

THREE MONTHS OR 500 HOURS

1.Remove access panels and screens.

2.Inspect the load resistors for mechanical break- down which is demonstrated by excessive sag- ging of the elements. Replace with new resistor elements as required.

3.Inspect for broken ceramic insulators. Replace with a new ceramic insulator if any cracks are found.

4.Inspect for loose hardware or loose connections. Tighten where required.

5.Inspect all connections for oxidation or corrosion. Clean the connection or replace the hardware where required.

6.Inspect all magnetic contactors to make sure that the contacts are not severely pitted or corroded. The contacts must move freely and be properly seated.

7.Clean all dirt and debris out of the load bank. This can be accomplished by blowing the inside of the unit with clean, dry compressed air (not to exceed 40 PSI). Eye protection should be worn when cleaning the Load Bank with compressed air.

8.Inspect all the wiring for any sign of insulation fail- ure.

9.Replace all access panels and screens. Tighten all the fastening hardware securely.

10.Check the indicator lamps on the control panel.

ANNUALLY

The blower motor should be lubricated according to the motor manufacturers' requirements and specifica- tions on the motor nameplate.

MASTER LOAD 750

Image 13
Contents Master Load California Proposition 65 Warnings Welding Equipment SafetyElectric Shock can kill Cylinder may explode if damaged Sûreté Pour Soudage a L’Arc Précautions DE SûretéLoad Bank Safety Thank You Table of Contents Description Technical Specifications Master Load General Description Safety PrecautionsBefore Installation InstallationPower Requirements LocationPurpose and USE of Controls OperationLoad Bank Operation Operating InstructionsRoutine and Period Maintenance MaintenanceHOW to USE Troubleshooting Guide Troubleshooting & RepairProblems Symptoms Possible CAUSES/REMEDIES Troubleshooting & Repair Troubleshooting & Repair Masterload 750 Wiring Diagram DiagramsMasterload 750 Dimension Print Parts Masterload 750 General AssemblyDescription QTY Item Description Page Page Page Precaucion Warnung