APC SUA500PDR manual Function Factory User Selectable Description Default Choices

Page 7

 

 

 

 

User Configurable Items

 

 

 

 

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

 

 

 

Low Battery

2 minutes

2, 5, 8, 11, 14,

 

PowerChute software interface provides

Warning

 

17, 20, 23 minutes

automatic, unattended shutdown when

 

 

 

 

approximately two minutes of battery operated

 

 

 

 

run time remains.

 

 

 

 

The low-battery warning beeps are continuous

 

 

 

 

when two minutes of run time remain.

 

 

 

 

Change the low battery warning interval setting

 

 

 

 

to the time that the operating system or system

 

 

 

 

software requires to safely shut down.

 

 

 

 

 

Synchronized

0 seconds

• 0 s

• 240 s

Specify the time the UPS will wait after the

Turn-on Delay

 

• 60 s

• 300 s

return of utility power before start up (to avoid

 

 

• 120 s

• 360 s

branch circuit overload).

 

 

 

 

 

• 180 s

• 420 s

 

 

 

 

 

 

High Transfer Point

120 V models:

 

 

To avoid unnecessary use of the battery where

 

127 VAC

• 127 VAC

• 133 VAC

utility voltage is chronically high, set the high

 

 

• 130 VAC

• 136 VAC

transfer point higher if the connected

 

 

equipment can tolerate this condition.

 

230 V models:

 

 

 

 

 

 

 

253 VAC

• 253 VAC

• 261 VAC

 

 

 

• 257 VAC

• 265 VAC

 

 

 

 

 

 

Low Transfer Point

120 V models:

 

 

To avoid unnecessary use of the battery where

 

106 VAC

• 97 VAC

• 103 VAC

utility voltage is chronically low, set the low

 

 

• 100 VAC

• 106 VAC

transfer point lower if the connected equipment

 

 

can tolerate this condition.

 

230 V models:

 

 

 

 

 

The SUA500PDRI ships ready for 230 V

 

208 VAC

• 196 VAC

• 204 VAC

 

sources. When operating the UPS in 208 V

 

 

• 200 VAC

• 208 VAC

 

 

applications, the UPS low transfer voltage

 

 

 

 

 

 

 

 

settings are adjusted through PowerChute

 

 

 

 

software or the Network Management Card.

 

 

 

 

The proper setting for low transfer voltage is

 

 

 

 

196 V.

 

 

 

 

Refer to the PowerChute user guide or the

 

 

 

 

Network Management Card instructions for

 

 

 

 

setting adjustment details.

 

 

 

 

 

Output Voltage

 

 

 

230 V models only: Sets the output voltage of

230 V models

230 VAC

• 220 VAC

• 240 VAC

the UPS while operating on battery.

 

 

• 230 VAC

 

 

 

 

 

 

 

7

Image 7
Contents Mount the UPS on DIN Rail Installation and Operation Smart-UPSSUA500PDRConnect Power and Equipment to the UPS Battery InstallationBranch circuit breaker is off prior to wiring the unit Emergency Power Off ConnectorsParameter Value UPS Display Panel Display Panel Indicators and Function ButtonsIndicator Indicator Title Description OperationBattery Charge Feature Feature Title Function ButtonUPS settings User Configurable ItemsFunction Factory User Selectable Description Default Choices Replacing the Battery Module Storage, Maintenance, TransportStorage Problem and/or Possible Cause Solution TroubleshootingAll LEDs are off and the UPS is wired to input utility power Problem and/or Possible Cause Solution APC Worldwide Customer Support ServiceTwo-Year Factory Warranty 990-4412