APC SUA500PDR manual Storage, Maintenance, Transport, Replacing the Battery Module

Page 8

Storage, Maintenance, Transport

Storage, Maintenance, Transport

Storage

Store the UPS covered in a cool, dry location with the batteries fully charged.

At 5° to 86° F (–15° to 30° C), charge the UPS batt ery every six months.

At 86° to 113° F (30° to 45° C), charge the UPS bat tery every three months.

Replacing the Battery Module

This UPS uses a replaceable, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure.

Ensure battery replacement every 2-4 years.

APCRBC135: Standard (40° C) battery

APCRBC136: High Temperature (50° C) battery

Once the batteries are disconnected the connected equipment is not protected from power outages.

Refer to the appropriate replacement battery installation guide for battery module installation instructions. See your dealer for information on replacement battery modules.

Be sure to deliver the spent battery(s) to a recycling facility or ship it to the address specified in the replacement battery literature.

8

Image 8
Contents Installation and Operation Smart-UPSSUA500PDR Mount the UPS on DIN RailBranch circuit breaker is off prior to wiring the unit Battery InstallationConnect Power and Equipment to the UPS Parameter Value ConnectorsEmergency Power Off Display Panel Indicators and Function Buttons Indicator Indicator Title DescriptionOperation UPS Display Panel Feature Feature Title Function Button Battery ChargeUser Configurable Items UPS settingsFunction Factory User Selectable Description Default Choices Storage Storage, Maintenance, TransportReplacing the Battery Module Troubleshooting Problem and/or Possible Cause SolutionAll LEDs are off and the UPS is wired to input utility power Problem and/or Possible Cause Solution Service APC Worldwide Customer SupportTwo-Year Factory Warranty 990-4412