Tripp Lite Extended-Run owner manual Battery and Breaker Diagrams +/- 240 VDC

Page 13

6– Diagrams (continued)

6-4 Battery and Breaker Diagrams (+/- 240 VDC)

Shelf 4 (Top)

 

Battery

 

Positive

Shelf 3

 

To UPS

 

Positive

 

To UPS

 

Negative

Battery

UL-Listed Breaker

Negative

To UPS

From Battery

Center Tap

Center Tap

Shelf 2

 

Shelf 1 (Bottom)

 

To Fuse or Breaker

To Center Tap

Termination

Termination

Notes:

All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.

Terminal block is UL-recognized and rated for 600 VDC.

Breaker is UL-listed and rated for 250 A, 600 VDC, 25 KAIC.

Cabinets with breakers are shipped with the breaker in the off/open position.

Battery arrangements shown are typical but may vary depending on cabinet and battery type.

[13]

Image 13
Contents Extended-Run 3-Phase Battery Cabinet Introduction FeaturesInstallation and Location Warnings Important Safety InstructionsConnection Warnings Battery Warnings Preparation Battery Cabinet InstallationTransportation Mechanical CheckBattery Cabinet Placement Internal Wiring TypicalPreliminary Electrical Check Electrical Connection Battery Charger Electrical Connection Select ModelsFinal Electrical Check Determine Charging Voltages Operation and ChargingInitial Charge Operational CheckMaintenance Schedule MaintenanceFuse Replacement Battery Cabinet Diagram 4 Shelves DiagramsBattery Cabinet Diagram 3 Shelves Battery and Breaker Diagrams 240 VDC Battery and Breaker Diagrams +/- 240 VDC 4 & 5Warning Do not connect the battery charger Integrated Battery Charger Select ModelsDimensions and Floor Loading SpecificationsRecommended Torque Warranty Storage and Service