6– Diagrams (continued)

6-5 Integrated Battery Charger (Select Models)

6.25 MAX

0.5

13.5

12.5

Terminal Block Detail

Input Voltage Selection

AC

L N

-

+

For 120 VAC Jumper:

Input

120

Output

 

2 & 3, 3 & 4, 5 & 6

 

VAC

 

 

For 208 VAC Jumper:

 

Output

 

 

 

 

 

 

1 & 2, 4 & 5

 

 

 

 

For 240 VAC Jumper:

2 & 3, 4 & 5Warning: Do not connect the battery charger

AC input to the UPS system output. The battery charger requires a separate AC supply circuit.

Notes:

All dimensions are inches.

AC input is selectable 120/208/240 VAC, 60 Hz.

Constant voltage output.

Electronic current limiting and high voltage shutdown.

AC and DC fusing. Included AC fusing is suitable for 120 VAC input.

Temperature compensation with remote battery temperature sensor.

Auxiliary output circuit for “Charger OK” indicator.

[14]

Image 14
Contents Extended-Run 3-Phase Battery Cabinet Features IntroductionConnection Warnings Important Safety InstructionsInstallation and Location Warnings Battery Warnings Transportation Battery Cabinet InstallationPreparation Mechanical CheckPreliminary Electrical Check Internal Wiring TypicalBattery Cabinet Placement Final Electrical Check Battery Charger Electrical Connection Select ModelsElectrical Connection Initial Charge Operation and ChargingDetermine Charging Voltages Operational CheckFuse Replacement MaintenanceMaintenance Schedule Diagrams Battery Cabinet Diagram 4 ShelvesBattery Cabinet Diagram 3 Shelves Battery and Breaker Diagrams 240 VDC Battery and Breaker Diagrams +/- 240 VDC Integrated Battery Charger Select Models 4 & 5Warning Do not connect the battery chargerRecommended Torque SpecificationsDimensions and Floor Loading Storage and Service Warranty