EX 5/7/11RT Systems

Table 5-7: Efficiency on ECO mode (all kinds of load) and batteries fully charged.

kVA / kW

25%

50%

75%

100%

Output load percentage

 

 

 

 

 

 

5kVA /

96

97

96

97

Output: 220 / 230 / 240 Volts

4kWatts

95

96

96

96

Output: 200 / 208 / 250 Volts

 

 

 

 

 

 

7kVA /

96

97

96

97

Output: 220 / 230 / 240 Volts

4.9kWatts

95

96

96

96

Output: 200 / 208 / 250 Volts

 

 

 

 

 

 

11kVA /

96

97

96

97

Output: 220 / 230 / 240 Volts

8kWatts

95

96

96

96

Output: 200 / 208 / 250 Volts

 

 

 

 

 

 

5.6Heat Rejection

Table 5-8: Full load heat rejection in BTU’s/hr.

System

 

Operation Mode

 

 

On-line

 

On Battery

 

5kVA

1350

 

1861

 

 

 

 

 

 

7kVA

1654

 

2280

 

 

 

 

 

 

11kVA

3033

 

3723

 

5.7Environmental Characteristics

The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.

The storage temperature: -20 to 40°C. Humidity: 5-95%, non condensing.

Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera- tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation due to the risk of thermal runaway.

Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.