MGE UPS Systems EX-5, EX-7, EX-11RT manual Battery Fault LED

Models: EX-7 EX-5, EX-7, EX-11RT

1 76
Download 76 pages 34.35 Kb
Page 58
Image 58

EX 5/7/11RT Systems

Table 4-2: Troubleshooting requiring MGE after-sales support.

Symptoms

Indication

Correction

LED

17

and 18 are on,

Internal fault

Call Customer Care (800) 438-7373.

Bypass AC Source is present

and transfer of load

(Hours: 24/7) or (800) 523-0142 (During

business

 

on Bypass AC source

business hours)

and audible alarm is on.

 

 

the LCD display shows:

 

 

xxx FAULT

 

 

 

 

 

 

 

 

LED

17

is on, and

Battery fault during the battery test.

Follow the battery replacement

audible alarm is on,

 

procedure in section 4.4.

the LCD display shows

 

 

BATTERY FAULT

 

 

 

 

 

 

 

LED

17

is on,

Static switch failure

Call the Customer Care Center.

the LCD display shows:

 

 

SHUTDOWN

 

 

STATIC SW FAILED

 

 

 

 

 

Audible alarm is on,

Batteries may have exceeded

Follow the battery replacement

the LCD display shows:

their rated life period. Battery

procedure in section 4.4.

END OF WARRANTY

capacity is severely reduced.

 

 

 

NOTE: To reset the alarm permanently, press both function buttons 21

and 22 for more than 3 seconds.

4 — 2

Maintenance

86-86000-00 B00

Page 58
Image 58
MGE UPS Systems EX-5, EX-7, EX-11RT manual Battery Fault LED