Installation and User Manual

2.7.2Connecting EX RT Transformer Module

(Part number 86211)

This module is to provide isolated 120/208/240 VAC outputs to the protected loads.

Figure 2-13: View of EX RT Transformer Module connected downstream for 120/208/240 Vac outputs (shown with one EXB).

BATTERY MODULE

EXB 5/7/11 RT

POWER MODULE

EX 5/7/11 RT

Transformer Module I/O Box

L3 L2 L1

Lb Ld N Lc La

TRANSFORMER

MODULE EX RT

 

 

AC Input from

AC Output to Load

 

 

(120VAC shown)

AC NORMAL

Power Module

 

(208VAC shown)

 

INPUT

TRANSFORMER MODULE

 

 

 

 

OUTPUT TO LOAD

WARNING

To avoid overloading transformer windings, provide branch over current

 

protection for all transformer output terminals.

 

To avoid overloading 120VAC output windings, distribute loads evenly

 

between Load 2 and Load 4 (on rear of Transformer Module ) and between

 

120VAC output terminals (Lb-N, La-N.)

 

 

 

Terminal Block Transformer Module Connection diagram (located on bottom of Transformer I/O Box)

 

 

 

 

 

L3

 

 

 

L2

L1

 

 

Lb

Ld

 

 

N

 

Lc

La

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208Vac

 

 

 

 

 

 

 

 

 

 

 

120Vac

 

 

 

 

120Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208Vac

 

 

 

 

 

 

 

 

 

 

 

240Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input

 

 

 

 

 

 

 

 

 

 

AC Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Block capability : AWG 4 solid or stranded wire.

Simplified Connection Diagram

UPSTREAM

Bypass AC

 

CIRCUIT

 

BREAKER

 

(NOT SUPPLIED)

 

AC INPUT

Normal AC

 

Transformer Module

To Load

86-86000-00 B00

Installation

2 — 15

Page 41
Image 41