Installation and User Manual

4.2Hot Swapping the Power Module

This operation can be performed without interrupting the load. Figure 4-1: Disconnecting the Power Module.

 

17

Stop the system with the OFF button

20

 

 

1.

 

 

 

(press more than 3 seconds). System is now

 

 

powered by Bypass AC source.

 

 

 

 

 

Check if UPS is on Bypass AC source by

 

 

XXX FAULT

verifying that:

 

 

 

 

 

 

 

 

 

1CXXXXXXX

LED 17 is ON (If LED 17 is not ON, do not

 

 

OFF

ON

turn the manual bypass and call the after sales

 

 

support department).

 

 

 

20

2.

Turn the manual bypass switch

7

to the

 

BYPASS position.

 

 

 

 

 

 

 

 

 

3.

Switch the battery circuit breaker(s)

14

to the

 

 

OFF position.

 

 

 

 

42

CAUTION: Do not switch the Normal AC

 

 

 

40

source circuit-breaker

8 to

 

7

the OFF position.

 

 

 

Doing so will disconnect

 

 

 

 

power to the load.

 

 

 

4. Loosen three screws to remove the

 

 

 

8 Step 4 in Tower

Input/Output box.

 

 

 

 

 

 

 

 

 

configuration

 

40 and

42

 

5.

Disconnect the battery cables

from the Power Module.

The Power Module can be replaced.

The connected equipment is powered by the

Bypass AC source.

Step 4 in Rack configuration.

86-86000-00 B00

Maintenance

4 — 3

Page 59
Image 59
MGE UPS Systems EX-5, EX-7, EX-11RT manual Hot Swapping the Power Module, 1CXXXXXXX