1.5.3Multiple Battery Module Backup Time at Full Load

Standard EX 5/7/11RT systems (one Power Module, and one Battery Module), offers a standard backup time of 5 to 12 minutes at full load.

To increase backup time, it is possible to connect up to 5 additional Battery Modules to the standard system. See section 2.8 for connections between standard system and Battery Module (EXB 5/7/11RT)

Figure 1-9: Typical back-up time with multiple EXB’s at full load.

Standard

 

Optional

EX 5/7/11RT systems

 

Configurations

 

 

 

 

 

 

 

 

 

EX 5/7/11RT EXB 5/7/11RT +

EXB 5/7/11RT +

EXB 5/7/11RT +

EXB 5/7/11RT

+

EXB 5/7/11RT

+

EXB 5/7/11RT

5 kVA

:

9 min

25 min

45 min

60 min

84 min

100 min

7 kVA

:

7 min

20 min

32 min

45 min

57 min

72 min

11 kVA:

 

5 min

14 min

22 min

30 min

42 min

53 min

See Appendix for additional Back-up time information.

1.5.4Battery Extension Cable Kit

(6 ft./1.8 m, Part number 86006)

This extended battery cable kit will be used instead of the standard battery cable when Battery Modules (EXBs) are distant from each other (located in two different enclosures, for instance).

The battery extension cable kit includes a 6 ft. long, straight connector battery power cable and a 6 ft. long battery detection cable.