Installation and User Manual

 

 

 

 

 

 

 

Table 3-1: Local Settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

Factory setting

 

Options

 

 

 

 

 

 

 

 

 

Language

English

 

French, Spanish, German, Italian

 

 

 

 

 

 

 

 

Date/time format

International

 

US

 

 

 

 

 

 

 

 

Date/time change

(DD-MM-YYYY/HH:MM)

MM-DD-YYYY/HH:MM adjustable

 

 

 

 

 

 

 

 

Audible alarm

Quick beeps

 

Slow beeps

 

 

 

 

 

 

 

 

Table 3-2: Output Features.

 

 

 

 

 

 

 

 

 

 

 

 

Display

Factory setting

Options

 

Comments

 

 

 

 

 

 

 

Output voltage

208 Volts AC (***)

200/208/220/230/240/250

Input voltage must be equal to

 

 

 

 

 

output voltage

 

 

 

 

 

 

 

 

Frequency converter

Disabled

Enabled

 

Bypass AC source disabled

 

 

 

 

 

 

 

 

Output frequency

Auto ranging

50/60 Hz

 

User selectable under

 

 

 

 

 

frequency converter mode

 

 

 

 

 

 

 

 

ECO mode

Disabled

Enabled

 

See section 3.4.2.

 

 

 

 

 

 

 

 

Hot standby

Disabled

Enabled

 

Full redundancy (see Figure 3-3)

 

 

 

 

 

 

 

 

Operating mode

Industrial

IT Network

 

(*) See Table 3-5.

 

 

 

 

 

 

 

Bypass

When bypass NOK

When bypass OK (**)

(*) See Table 3-5.

 

Transfer

 

 

 

 

 

 

 

 

 

 

 

 

Interrupt time

10 ms

10 to 200 ms

Interrupt time calibration during

 

 

 

(by steps of 10 ms)

during load transfer when

 

 

 

 

 

Bypass AC source

 

 

 

 

 

is out of tolerances

 

 

 

 

 

 

 

 

Overload level

102%

50/70%

 

 

 

(*): - Select "IT Network" for computer loads. Select “Industrial” for other applications or when there exists and absolute need for service continuity (with potential 10msec. interrupt) when Bypass AC source is not within set tolerances.

See table 3-5 for more details

(**)UPS will switch to Bypass AC Source if it is within the set tolerances. (***) Input voltage must be equal to output voltage.

Figure 3-3: Configuration used to provide cascade redundancy to critical loads.

BYPASS AC

Protective Device

NORMAL AC

Utility

AC Source

Protective Device NORMAL AC

Cascade redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.

LOAD

86-86000-00 B00

Operation

3 — 3

Page 49
Image 49
MGE UPS Systems EX-5, EX-7, EX-11RT manual Display Factory setting Options Comments