EX 5/7/11RT Systems

NOTE:

This step is unique to the Power Module. It involves the installation of the I/O Box

 

Bracket System.

 

 

The I/O Box bracket system keeps the I/O Box stationary while hot swapping the Power Module. It will then be easier to slide the replacement module into the connectors of the I/O Box.

1&2. Secure small brackets to larger bracket from the underside 27 .

3.Secure small attached brackets to the I/O Box with four screws.

4. Secure large bracket 27 to rails at the rear of module with four nuts.

Figure 2-7: Input/Output Box Bracket System.

1

2

4

4

3

Install input/output cables

per section 2.7 prior to this step.

2 — 8

Installation

86-86000-00 B00

Page 34