MGE UPS Systems EX-5, EX-7, EX-11RT manual Symptoms IT Network mode Industrial mode

Models: EX-7 EX-5, EX-7, EX-11RT

1 76
Download 76 pages 34.35 Kb
Page 51
Image 51

Installation and User Manual

3.3Information Technology IT Network and Industrial Operating Modes

Table 3-5: System Operation in IT Netowrk and Industrial Modes.

Symptoms

IT Network mode

Industrial mode

Overload, and Bypass

Load is transferred to Bypass AC source.

source in tolerance.

UPS returns to normal mode if overload

 

is removed.

Same as IT Network mode, but AC to the UPS does not return to normal mode if overload

is removed.

Overload, and Bypass

The UPS shuts down and load is not

Load is transferred to Bypass

AC source not in tolerance.

transferred to Bypass AC source.

AC source with 10 milli-

 

 

seconds output break.

 

 

The UPS does not return to

 

 

normal mode if overload

 

 

is removed.

Output short circuit and Bypass

The load remains powered by the UPS.

Load is transferred to Bypass

AC source in tolerance.

The UPS shuts down after 3 minutes

AC source. The UPS does not

 

if the short circuit remains.

return to normal mode if the

 

 

short circuit is removed.

Output short circuit and Bypass AC source not in tolerance.

The load remains powered by the UPS. The UPS shuts down after 3 minutes if the short circuit remains.

The load is transferred to Bypass AC source with

10 milliseconds output break. The UPS does not return to normal mode if the short circuit is removed.

86-86000-00 B00

Operation

3 — 5

Page 51
Image 51