EX 5/7/11RT Systems

2.7.3Connections with Separate Normal and Bypass AC sources (2 Mains)

CAUTION:

This connection requires isolation Transformer Module. Call MGE

 

Technical Support for details.

 

 

Figure 2-14: Normal AC and Bypass AC inputs, Output Cables Installation, and Simplified Connection Diagram.

O

1

OFF

 

L3

L1

OFFO

2

Bypass

3 Output Normal

4

OFF

O

66074

To Load or

Transformer Module (if applicable)

Proceed as follows:

1.Remove the cover plate under the I/O Box. Loosen the terminal blocks L1 and L3, and remove the jumper.

CAUTION:

Always connect the earth ground wire

 

first.

2.Install Normal AC, Bypass AC and output cables as shown.

3.Reinstall the cover plate under the I/O Box with four screws.

4.Secure the I/O Box to the Power Module with three screws.

See section 2.7.2 for connecting EX RT Transformer module, if applicable.

With separate Normal and Bypass AC inputs, supplied by separate sources.

BYPASS AC

MAINS 2

 

Isolation

 

Transformer

 

(PN 86211)

MAINS 1

LOAD

 

NORMAL AC

2 — 16

Installation

86-86000-00 B00

Page 42
Image 42
MGE UPS Systems EX-5, EX-7, EX-11RT manual Bypass AC Mains