Appendix
5.0Electrical Specifications
Electrical and Mechanical specifications for the EX 5/7/11RT.
5.1System Input/Output Power Ratings
Table
Source | Voltage |
| Frequency | |
Normal AC Source | 156 to 280 | VAC | 40 to 70 | Hz |
Bypass AC Source | 160 to 242 | VAC* | 58 to 62 | Hz** |
|
|
| ||
Load Output | 200/208/220/230/240/250VAC | 50/60 Hz autoranging | ||
| (120/208/240Vac | (or frequency converter) | ||
| are possible with |
|
| |
| transformer module) |
|
|
(*): depends on output voltage setting, can be modified by software.
(**): set to +/- 4% by default, (1, 2, 4, 8% are possible values), can be modified by software.
5.2System Overload Characteristics
Figure 5-1: Power supplied as a function of input voltage (left), and permissible UPS overloads as a function of time (right).
100%
70%
Load Percentage | Load Percentage |
| ||
|
|
|
| |
| 1.5 |
|
|
|
| 1.25 |
|
|
|
| 1.1 |
|
|
|
| 1.02 |
|
| t |
U |
|
|
| |
0.5s | 30s | 60s | 120s |
120V 160V | 280V |
Appendix | 5 — 1 |