Bryant R-410A warranty SPECIFICATIONS Continued

Page 5

SPECIFICATIONS Continued

UNIT SIZE-SERIES

042-A

 

048-A

 

060-A

Operating Weight (Lb)

215

 

217

 

278

 

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

 

Unit Volts— Hertz— Phase

 

208/230-60-1

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range*

 

187-253

 

 

 

 

 

 

 

 

 

 

Compressor— Rated Load Amps

19.9

 

24.4

 

30.1

 

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

127.0

 

131.0

 

172.0

 

 

 

 

 

 

 

 

 

Condenser Fan Motor— Full Load Amps

1.10

 

1.40

 

1.40

 

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

24.4

 

26.7

 

35.9

 

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

10

 

8

 

8

 

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

10

 

10

 

8

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

77

 

97

 

80

 

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

73

 

59

 

76

 

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

 

Circuit Breaker Size (Amps)

40

 

50

 

60

 

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

 

Compressor— Type

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manufacturer

 

 

Copeland

 

 

 

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

 

Internal Line Break

 

 

 

 

 

 

 

 

 

 

 

Refrigerant— Type

 

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

 

 

 

Amount (Lb)

6.33

 

6.83

 

7.93

 

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

 

Coil Face Area (Sq Ft)

12.16

 

12.16

 

18.3

 

 

 

 

 

 

 

 

 

Fins per In.— Rows— Circuits

25— 1— 2

 

25— 1— 2

 

25— 1— 3

 

 

 

 

 

 

 

 

 

Fan Motor— HP (PSC) & RPM

1/5 & 825

 

1/4 & 1100

 

1/4 & 1100

 

 

 

 

 

 

 

 

 

Volts— Hertz— Phase

 

208/230-60-1

 

 

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

2800

 

3400

 

3400

 

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

Support Feet

 

 

KSASF0101AAA

 

 

 

 

 

 

 

 

 

 

 

Coastal Filter

 

 

KAACF0801MED

 

 

 

 

 

 

 

 

 

 

 

Time Delay Relay

 

 

KAATD0101TDR

 

 

 

 

 

 

 

 

 

 

 

Cycle Protector

 

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

KAACH1201AAA

 

 

 

 

 

 

 

 

 

 

Start Assist— Capacitor/Relay Type

 

KSAHS1501AAA

 

KSAHS1601AAA

 

 

 

 

 

 

 

 

 

Start Assist— PTC Type

 

 

KAACS0201PTC

 

 

 

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

KSATX0301HSZ

 

KSATX0401HSZ

 

KSATX0501HSZ

 

 

 

 

 

 

 

 

 

Piston Body

 

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

 

 

 

Filter Drier (Suction Line) (RCD)

 

 

KH45LG141

 

 

 

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat††

 

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

 

KAALS0201LLS

 

 

 

 

 

 

 

 

 

 

 

Winter Start Control††

 

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

 

KSALA0301410

 

 

 

 

 

 

 

 

 

 

 

MotorMaster® Control**

 

 

32LT660004

 

 

 

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor (RCD)

HC38GE231

 

 

HC40GE232

 

 

 

 

 

 

 

 

 

Thermostat— Auto Changeover,

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-B

 

 

 

 

 

 

 

 

 

 

 

Thermostat— Auto Changeover,

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

 

 

 

 

 

 

 

 

 

 

Thermidistat™ Control—

 

 

 

 

 

Programmable Thermostat with Humidity Control

 

 

TSTATBBPRH01-B

 

 

 

 

 

 

 

 

 

 

 

Builder’s Thermostat— Manual Changeover,

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

 

 

 

Thermostat Conversion Kit (4 to 5 wire)— 10 Pack

 

 

TSTATXXCNV10

 

 

 

 

 

 

 

 

 

 

 

*Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. ** Fan motor with ball bearings required.

††See low-ambient controller Installation Instructions for application.

N/A — Not Applicable.

NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

— 5—

Image 5
Contents 591B 60 Hz AVAILABLE OPTIONSDELUXE 11 SEER AIR CONDITIONERDIMENSIONS IN DIMENSIONSCHECK-FLO-RATER PISTON RECOMMENDED TUBE DIAMETERSCHARGING SUBCOOLING TXV-TYPE EXPANSION DEVICE WHEN THE COMPLETE SYSTEMUNIT SIZE-SERIES SPECIFICATIONS018-A 024-ASPECIFICATIONS Continued ACCESSORY DESCRIPTION AND USAGE Listed Alphabetically ACCESSORY USAGE GUIDELINESOUND POWER dBA A-WTD, WITHOUT PURE TONE PENALTY ACCESSORY DESCRIPTION AND USAGE Listed Alphabetically ContinuedLEVEL SIZECOMBINATION RATINGS COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued Tested combination 591BN018-A Outdoor Section With CC5A/CD5AA024 Indoor Section DETAILED COOLING CAPACITIES591BN024-A Outdoor Section With CC5A/CD5AA030 Indoor Section 591BN030-A Outdoor Section With CC5A/CD5AA036 Indoor Section DETAILED COOLING CAPACITIES* Continued591BN036-A Outdoor Section With CC5A/CD5AA042 Indoor Section 591BN036-A Outdoor Section With CC5A/CD5AA042 Indoor Section 591BN042-A Outdoor Section With CC5A/CD5AA048 Indoor Section 591BN048-A Outdoor Section With CC5A/CD5AA060 Indoor Section 591BN060-A Outdoor Section With CC5A/CD5AW060 Indoor Section 591BN018-A CONDENSER ONLY RATINGS591BN024-A 591BN030-A591BN036-A CONDENSER ONLY RATINGS* Continued591BN042-A 591BN048-ASYSTEM DESIGN SUMMARY 591BN060-AA98599 MATCHED SYSTEMPage Warranty for inclusion by specifying engineer GUIDE SPECIFICATIONSOperating Characteristics Special Features