Bryant R-410A Guide Specifications, General, Products, System Description, Quality Assurance

Page 28
GUIDE SPECIFICATIONS

GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a her- metic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI Standard 210.

Unit will be certified for capacity and efficiency, and listed in the lastest ARI directory.

Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c-UL approval.

Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 150 psig and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge Puron® (R-410A), and special features required prior to field start-up.

Refrigerant

Refrigerant will be Puron (R-410A) HFC Refrigerant with zero ozone depletion potential. R-410A is approved under the EPA’s Significant New Alternatives Program (SNAP).

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Air-Cooled, Split-System Air Conditioner 591B

1-1/2 to 5 Tons Nominal

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.

Fan blades will be statically and dynamically balanced.

Condenser fan openings will be equipped with PVC-coated steel wire safety guards.

Compressor

Compressor will be hermetically sealed.

Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.

Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line shutoff valve with sweat connections, vapor-line shutoff valve with sweat connections, system charge of Puron® (R-410A) refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a

suction temperature of _____ °F. The power consumption at full

load will not exceed _____ kW.

Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at

conditions of _____ CFM entering air temperature at the

evapo-rator at _____ °F wet bulb and _____ °F dry bulb, and

air enter-ing the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or greater at

DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single

phase, 60 Hz. The unit will be capable of satisfactory opera-tion within voltage limits of _____ v to _____ v.

Unit electrical power will be single point connection. Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS

Cancels: New

© 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231

— 28—

PRINTED IN U.S.A. Catalog No. 5259-100 9-01

Image 28
Contents AVAILABLE OPTIONS 591B 60 HzDELUXE 11 SEER AIR CONDITIONERDIMENSIONS DIMENSIONS INRECOMMENDED TUBE DIAMETERS CHECK-FLO-RATER PISTONCHARGING SUBCOOLING TXV-TYPE EXPANSION DEVICE WHEN THE COMPLETE SYSTEMSPECIFICATIONS UNIT SIZE-SERIES018-A 024-ASPECIFICATIONS Continued ACCESSORY USAGE GUIDELINE ACCESSORY DESCRIPTION AND USAGE Listed AlphabeticallyACCESSORY DESCRIPTION AND USAGE Listed Alphabetically Continued SOUND POWER dBA A-WTD, WITHOUT PURE TONE PENALTYLEVEL SIZECOMBINATION RATINGS COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued Tested combination DETAILED COOLING CAPACITIES 591BN018-A Outdoor Section With CC5A/CD5AA024 Indoor Section591BN024-A Outdoor Section With CC5A/CD5AA030 Indoor Section DETAILED COOLING CAPACITIES* Continued 591BN030-A Outdoor Section With CC5A/CD5AA036 Indoor Section591BN036-A Outdoor Section With CC5A/CD5AA042 Indoor Section DETAILED COOLING CAPACITIES* Continued 591BN042-A Outdoor Section With CC5A/CD5AA048 Indoor Section 591BN048-A Outdoor Section With CC5A/CD5AA060 Indoor Section 591BN060-A Outdoor Section With CC5A/CD5AW060 Indoor Section CONDENSER ONLY RATINGS 591BN018-A591BN024-A 591BN030-ACONDENSER ONLY RATINGS* Continued 591BN036-A591BN042-A 591BN048-A591BN060-A SYSTEM DESIGN SUMMARYMATCHED SYSTEM A98599Page GUIDE SPECIFICATIONS Warranty for inclusion by specifying engineerOperating Characteristics Special Features