Bryant 764A Service Cleaning, Unit Top Removal, Repairing Refrigerant Leaks, III. Condenser FAN

Page 15

SERVICE

NOTE: The following steps should be performed by a quali- ®ed service person.

WARNING: Before installing or servicing unit, turn off main power to system to avoid shock hazard or in- jury from rotating parts. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury or death.

I. CLEANING

Inspect unit interior at the beginning of each heating and cool- ing season or as operating conditions require. To inspect and clean, the unit top must be removed.

A. Unit Top Removal

NOTE: When performing maintenance or service procedures that require removal of the unit top, be sure to perform all of the routine maintenance procedures that require top re- moval, including: coil inspection and cleaning, and conden- sate drain pan inspection and cleaning.

Only quali®ed service personnel should perform mainte- nance and service procedures that require unit top removal. Refer to the following top removal procedures:

1.Remove 7 screws on unit top cover surface. Save all screws.

2.Remove 2 screws that secure unit top cover ¯ange. Save all screws.

3.Lift top from unit carefully. Set top on edge and ensure that top is supported by unit side that is opposite duct side.

When maintenance and/or service procedures are concluded, carefully replace and secure unit top to unit, using screws re- moved in Steps 1 and 2.

B. Repairing Refrigerant Leaks

Proceed as follows to repair a refrigerant leak and to charge the unit.

1.Locate leak and ensure that refrigerant system pres- sure has been relieved and recovered from both high- and low-pressure ports.

2.Repair leak following accepted practices.

NOTE: Install a ®lter drier whenever the system has been opened for repair.

3.Add a small charge of nitrogen vapor to system and leak- test unit.

4.Evacuate refrigerant system if additional leaks are not found.

5.Charge unit with R-22 refrigerant, using a volumetric- charging cylinder or accurate scale. Refer to unit rating plate for required charge. Be sure to add extra refrig- erant to compensate for internal volume of ®lter drier.

NOTE: See Adjusting Refrigerant Charge on page 16.

C.Condenser Coil, Evaporator Coil, and Condensate Drain Pan

WARNING: Be careful! Coil ®ns are sharp. Protect hands with gloves when cleaning or handling coil.

Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year. Proper inspection and clean- ing requires the removal of the unit top. See Unit Top Removal section above.

The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions (including weeds and shrubs) that interfere with the air¯ow through the condenser coil. Straighten bent ®ns with a ®n comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using a soft brush attachment. Be careful not to bend the ®ns. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air ®lter(s). For best results, spray condenser-coil ®ns from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to ¯ush all dirt and debris from the unit base.

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air ®lter(s). If the drain tube is restricted, clear it with a ``plumbers snake'' or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.

II. EVAPORATOR FAN AND MOTOR

Refer to Care and Maintenance section for procedure.

III. CONDENSER FAN

CAUTION: Keep the condenser fan free from all obstructions to ensure proper cooling operation. Never place articles on top of the unit. Damage to unit may result.

1.Shut off unit power supply.

2.Remove condenser-fan assembly (grille, motor, motor cover, and fan) by removing screws and ¯ipping assembly onto unit top cover.

3.Loosen fan hub setscrews.

4.Adjust fan height as shown in Fig. 18.

5.Tighten setscrews.

6.Replace condenser-fan assembly.

Fig. 18 Ð Condenser-Fan Adjustment

Ð15Ð

Image 15
Contents Installation Important Ð Read Before InstallingContents Safety ConsiderationsÐ2Ð Base Unit Dimensions Ð 564A/764A024-036Ð3Ð Base Unit Dimensions Ð 564A/764A042,048Ð4Ð Base Unit Dimensions Ð 564A/764A060II. RIG and Place Unit Ground-Level InstallationLocate the Unit ClearancePhysical Data Field-Duct ConnectionsÐ6Ð Ð7Ð Shipping Location of Duct Flanges Size 060 OnlyDo not USE Aluminum Wire Electrical ConnectionsÐ8Ð Unit Electrical Connection Entry Holes Control Box WiringFLA MCA Mocp LRA Electrical DataPRE-START-UP Accessory InstallationII. Cooling Section START-UP and Adjustments START-UP Heating Section START-UP and AdjustmentsIII. Indoor Airflow and Airflow Adjustments Care and Maintenance AIR FilterII. Evaporator FAN and Motor Condenser Coil, Evaporator Coil, and Condensate Drain Pan Service CleaningRepairing Refrigerant Leaks Unit Top RemovalVI. Metering Device Servicing IV. Electrical Controls and WiringIX. Replacement Parts Indoor AirflowCooling Charging Chart Ð 564A/764A024 Cooling Charging Chart Ð 564A/764A048 Symptom Cause Remedy Cooling Troubleshooting ChartPage Page Packaged Service Training Page III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information

764A specifications

The Bryant 764A is a high-performance air conditioning and heating system that exemplifies efficiency and reliability for residential and commercial use. Designed to deliver optimal comfort in various climates, the 764A is known for its impressive energy efficiency ratings and advanced technologies.

One of the standout features of the Bryant 764A is its variable speed compressor. This innovative component allows the system to adjust its output according to the specific cooling or heating demands of the environment. By operating at different speeds, the compressor can maintain a consistent indoor temperature while using less energy compared to traditional single-stage systems. This not only enhances comfort but also contributes to significant energy savings over time.

The Bryant 764A is equipped with a smart thermostat that offers precise control over indoor climates. This thermostat can be programmed to adjust temperatures based on user preferences and schedules, further improving energy efficiency. Users can also control the system remotely via a smartphone app, ensuring comfort is just a tap away.

In terms of its construction, the Bryant 764A is built with durability in mind. The unit features a robust cabinet designed to withstand harsh weather conditions, which extends the lifespan of the system. Additionally, its sound-dampening technology minimizes operational noise, creating a more peaceful indoor environment.

The 764A incorporates advanced filtration systems to improve indoor air quality. With allergen filtration capabilities, it effectively reduces dust, pollen, and other airborne particles, making it an excellent choice for allergy sufferers. This focus on air quality aligns with Bryant's commitment to creating healthier living spaces.

Moreover, the Bryant 764A is designed with environmentally friendly refrigerants, aligning with modern standards for reducing greenhouse gas emissions. This commitment to sustainability is becoming increasingly important for consumers looking to reduce their environmental footprint.

Overall, the Bryant 764A stands out as a comprehensive solution for heating and cooling needs. With its variable speed technology, smart thermostat, durable construction, and focus on air quality, it offers both efficiency and comfort, making it a wise investment for any property owner looking to enhance their indoor environment.